Beam Deflection Calculator: Deflection, Moment, Shear and Reactions
By FindMySum · Last reviewed
Every beam bends under load. How far it bends, the deflection, decides whether a floor feels solid, whether drywall cracks and whether a shelf sags. This beam deflection calculator works out the deflected shape of a beam on four kinds of supports, under any combination of a point load, a uniform load and a partial uniform load, and reports the maximum deflection, bending moment, shear and support reactions, with serviceability checks against L/360, L/240 and L/180. It works in metric or imperial units, and it takes E for sawn lumber, steel or aluminium and I from the beam's cross-section.
The beam equation
For a linear elastic beam with small deflections, the curvature at each point is the bending moment divided by the flexural rigidity:
EI × d²y/dx² = M(x)
E is the material's modulus of elasticity and I the second moment of area of the cross-section. The calculator finds the reactions, builds the shear and moment along the beam by statics, then integrates M ÷ EI twice, with the end conditions of your supports: zero deflection at a pin, zero deflection and slope at a fixed end. The textbook formulas are special cases:
- simply supported, uniform load: δ = 5wL⁴ ÷ 384EI, M = wL²/8
- simply supported, point load at midspan: δ = PL³ ÷ 48EI, M = PL/4
- cantilever with a tip load: δ = PL³ ÷ 3EI; with a uniform load: δ = wL⁴ ÷ 8EI
- fixed at both ends, uniform load: δ = wL⁴ ÷ 384EI, end moments wL²/12
Worked example: a floor joist
The calculator opens with a 2×10 spruce-pine-fir joist, 38 × 235 mm, spanning 3.6 m and carrying 1 kN/m, a rough figure for a joist at 400 mm spacing under a residential floor load.
- I = bh³ ÷ 12 = 38 × 235³ ÷ 12 = 41.1 × 10⁶ mm⁴
- E = 9,500 MPa for S-P-F No. 1/No. 2 (CSA O86)
- δ = 5 × 1.0 × 3,600⁴ ÷ (384 × 9,500 × 41.1 × 10⁶) = 5.6 mm at midspan
- M = 1.0 × 3.6² ÷ 8 = 1.62 kN·m; each support carries 1.8 kN
The span divided by the deflection is 643, so the joist is well inside L/360 (10 mm) for this load. Double the span to 7.2 m and the deflection rises sixteenfold to about 90 mm, because it depends on the fourth power of the span.
Supports
- Simply supported: free to rotate at both ends, the usual model for joists resting on walls or beams.
- Cantilever: fixed at the left end and free at the right, like a balcony or a shelf bracket. Deflection is largest at the tip, and the fixed end carries a large hogging moment.
- Fixed at both ends: restrained against rotation at both supports. Five times stiffer than a simple span under a uniform load, but the connections must resist end moments of wL²/12.
- Propped cantilever: fixed at the left and pinned at the right. The calculator solves the indeterminate reaction by requiring zero deflection at the prop.
Loads
Enter any combination: a uniform load over the full span, a point load at any position, and a partial uniform load between two points. Results are combined by superposition, which is exact for linear elastic beams. An off-centre point load produces its largest deflection between the load and midspan, not under the load: 10 kN at 2 m on a 6 m steel beam deflects most at about 2.73 m.
Reading the results
The headline gives the largest deflection and where it occurs. The cards give the largest bending moment (sagging positive, hogging negative), the largest shear and the reactions, with fixed-end moments where there are any. The chart shows the deflected shape, and the table lists shear, moment and deflection at tenths of the span. The checks table compares the deflection with the common limits; which limit applies depends on the use and on the code.
Materials and sections
Choose a lumber species group (moduli from CSA O86 for No. 1/No. 2 grade), structural steel (210 GPa) or aluminium (70 GPa), or enter your own E. For the section, choose a rectangle, an I-beam, a rectangular tube or a solid round bar and enter its dimensions, or type in I from a steel section table. Remember that dressed lumber is smaller than its name: a 2×10 is 38 × 235 mm (1.5 × 9.25 in).
Limits
This is elastic beam theory, not a design. It does not check bending or shear stress against the material's strength, apply load factors and combinations, allow for creep in wood under long-term load, or check lateral buckling, bearing at supports, notches, or floor vibration. In Canada, joists, rafters and beams in houses are sized from the span tables in Part 9 of the National Building Code or your provincial code; anything else needs a professional engineer.
More questions
Why do floors feel bouncy even when they meet code?
Deflection limits like L/360 control how far a floor sags under its design load, but bounciness depends on stiffness and the floor's natural frequency under footsteps. Long spans of lightweight joists can meet L/360 and still feel lively. Blocking or bridging between joists, a thicker subfloor glued down, or deeper joists stiffen the system.
What is the difference between deflection and strength?
Deflection is how far a beam bends under load; strength is whether it breaks or yields. A beam can be strong enough but too flexible, or stiff enough but overstressed, especially for short spans with heavy point loads. Design checks both: stresses against the material's strength with load factors, and deflection against serviceability limits.
Does wood deflect more over time?
Yes. Under a sustained load, wood creeps: the deflection keeps growing, often by half again or more over years, especially in damp conditions. Design standards increase the long-term deflection for permanent loads for this reason. Steel does not creep at normal temperatures; concrete does.
What is a propped cantilever?
A beam fixed against rotation at one end and simply supported at the other, such as a beam built into a wall at one end and resting on a post at the other. It is statically indeterminate: the support reactions depend on the beam's stiffness, not just on statics. Under a uniform load, three eighths of the load goes to the propped end.
How do I include the beam's own weight?
Add it to the uniform load. A 2×10 S-P-F joist weighs about 0.04 kN/m; a W250×33 steel beam 33 kg/m, or about 0.32 kN/m. For long or heavy beams the self-weight can be a significant part of the total.
What do the shear and moment diagrams tell me?
The shear diagram shows the internal force trying to slide one part of the beam past the other; the moment diagram shows the internal bending. The largest moment, usually where the shear crosses zero, sets the bending stress. The largest shear, usually at the supports, matters for short, heavily loaded beams and for notched wood members.
Sources
This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.