Power Factor Calculator

Calculate power factor, kW, kVAR and kVA for single- and three-phase loads, and the capacitor kVAR and µF needed to correct it at 60 Hz, including 347/600 V.

Calculator Details

Power factor:0.8See results ↓

Single phase (S = VI) or balanced three phase (S = √3 V_LL I)

60 Hz in Canada and the US, 50 Hz in most other countries

Real power and power factor, voltage, current and power factor, or measured kW, volts and amps

Power the load actually uses, in kilowatts

Line-to-line for three phase: 120, 208, 240, 347, 480 or 600 V are common in Canada

From 0 to 1 (0.8 = 80%), lagging for motors and other inductive loads

Utilities often ask for 0.90 to 0.95

Your Results

Power factor: 0.8

Power factor

0.8

80% · φ = 36.87° lagging

Real power (P)

50 kW

Reactive power (Q)

37.5 kVAR

Apparent power (S)

62.5 kVA

60.141 A per line

Capacitors to reach 0.95

21.07 kVAR

51.74 µF per phase in delta, 155.2 µF in wye

Current after correction

50.645 A

15.8% less

Billed demand (Hydro-Québec rule)

56.25 kW

50 kW after correction

The power factor is 0.8 (50 kW of 62.5 kVA, with 37.5 kVAR reactive). Raising it to 0.95 takes 21.07 kVAR of capacitors and cuts the current by 15.8%.

Compare scenarios

Save these inputs as a scenario, change them, and compare the results side by side.

Loading, available in a moment

Power triangle before and after correction

Power triangle before and after correction

Detailed Breakdown

Before and after correction to 0.95
QuantityNowCorrected
Real power (P)50 kW50 kW
Reactive power (Q)37.5 kVAR16.434 kVAR
Apparent power (S)62.5 kVA52.632 kVA
Line current (I)60.141 A50.645 A
Power factor0.80.95

Billed demand under Hydro-Québec's domestic, small- and medium-power rates (for example Rate G and Rate M): the higher of kW and 90% of kVA.

How This Calculator Works

How It’s Calculated

S = √3 × V × I · P = S × PF · Q = √(S² − P²) · PF = cos φ
Q_c = P × (tan φ₁ − tan φ₂) · C = Q_c ÷ (3 × 2πf × V²) per phase (delta)

Your calculation: S = 62.5 kVA and P = 50 kW, so PF = 50 ÷ 62.5 = 0.8 and Q = √(62.5² − 50²) = 37.5 kVAR. To reach 0.95: Q_c = 50 × (0.75 − 0.3287) = 21.07 kVAR.

Frequently Asked Questions

What is power factor?

The ratio of real power, which does useful work (kW), to apparent power, the volts times amps the supply must deliver (kVA): PF = P ÷ S. For a sinusoidal supply it equals cos φ, where φ is the angle by which the current lags (or leads) the voltage. A PF of 1 means every amp does useful work.

How do I calculate kVA, kW and kVAR?

Single phase: S = V × I ÷ 1000 kVA. Three phase: S = √3 × V_line × I ÷ 1000. Then P = S × PF and Q = √(S² − P²). A 240 V, 20 A single-phase load at PF 0.70 draws 4.8 kVA, uses 3.36 kW and circulates 3.428 kVAR.

How do I size a capacitor bank for power factor correction?

kVAR needed = kW × (tan φ₁ − tan φ₂), with φ₁ = acos(present PF) and φ₂ = acos(target PF). Raising 100 kW from 0.75 to 0.95 needs 55.32 kVAR. On a 480 V three-phase, 60 Hz system that is 212.3 µF per phase in delta.

Why does low power factor cost money?

The extra current heats cables and transformers and uses up their capacity, so many utilities charge for it. Hydro-Québec, for example, bills power demand on its domestic, small- and medium-power rates (for example Rate G and Rate M) as the higher of kW and 90% of kVA. The default 50 kW load at PF 0.80 is billed on 56.25 kW; corrected to 0.95 it is billed on 50 kW.

How much does correction reduce the current?

Current is proportional to kVA, so it falls with the apparent power. The default 600 V three-phase load drops from 60.14 A to 50.64 A when corrected from 0.80 to 0.95, 15.8% less, and the I²R heating in the feeders falls with the square of the current.

What voltages are used in Canada?

Homes get 120/240 V single phase. Commercial buildings commonly have 120/208 V three phase, and larger buildings and industry 347/600 V, which is distinctively Canadian (the US uses 277/480 V). All are 60 Hz. For three phase, enter the line-to-line voltage (208, 480 or 600 V).

Should I correct to a power factor of 1?

Usually not. The last few percent need disproportionately large capacitors (tan φ changes slowly near PF 1), and if the load drops the capacitors can push the power factor leading and raise the voltage. Targets of 0.95 to 0.98 are common. Large banks switch in steps or use automatic controllers.

Does this work for loads with harmonics, like drives and LED drivers?

Only partly. This calculator assumes sinusoidal voltage and current (displacement power factor). Variable-frequency drives, rectifiers and switch-mode supplies draw distorted current; their true power factor is lower, and adding plain capacitors can create harmonic resonance. Those cases need a harmonic study and detuned or active filters.

Uses the IEEE Std 1459-2010 sinusoidal power definitions (OpenStax University Physics Vol. 2 §15.5) for a balanced three-phase or a single-phase load with lagging (inductive) power factor. The billing figure applies one example rule, Hydro-Québec’s higher of kW and 90% of kVA (rate glossary, read 2026-11-10); your utility’s tariff may differ. It leaves out harmonics and true power factor, unbalanced loads, leading power factor, capacitor voltage ratings, detuning reactors and switching steps. Size real capacitor banks with an electrician or engineer and the manufacturer’s data.

Power Factor Calculator: kW, kVA, kVAR and Capacitor Sizing

By FindMySum · Last reviewed

In an AC circuit, not all the current a load draws does useful work. Motors, transformers and fluorescent ballasts also draw reactive current to build their magnetic fields, and that current flows back and forth without delivering energy. Power factor measures how much of the current is doing work. This power factor calculator works out the power triangle for single- and three-phase loads, the line current, and the capacitor bank that brings the power factor up to a target.

The power triangle

Three powers describe an AC load:

  • Real power P (kW): the rate at which energy is used, turned into motion, heat or light.
  • Reactive power Q (kVAR): energy that sloshes between the supply and the load's magnetic or electric fields every cycle.
  • Apparent power S (kVA): the volts times amps the supply must deliver, S² = P² + Q².

Power factor is PF = P ÷ S = cos φ, where φ is the phase angle between voltage and current. The apparent power is:

  • single phase: S = V × I
  • balanced three phase: S = √3 × V_line-to-line × I

Worked example: the default

The calculator opens with a 50 kW load at PF 0.80 on a 600 V three-phase supply, a typical small Canadian plant.

  • S = 50 ÷ 0.80 = 62.5 kVA
  • Q = √(62.5² − 50²) = 37.5 kVAR
  • φ = acos 0.80 = 36.9°
  • Current: 62,500 ÷ (√3 × 600) = 60.1 A

To raise the power factor to 0.95, capacitors must supply part of the reactive power locally:

  • tan φ₁ = 37.5 ÷ 50 = 0.750; tan φ₂ = tan(acos 0.95) = 0.329
  • Q_c = 50 × (0.750 − 0.329) = 21.1 kVAR

After correction the load draws 52.6 kVA and 50.6 A, almost 16% less current. Real power doesn't change: the motors do the same work.

Capacitor size in microfarads

A capacitor of C farads at voltage V and frequency f supplies Q = 2πf · C · V² vars. So:

  • single phase: C = Q_c ÷ (2πf V²)
  • three phase, delta-connected (each capacitor across two lines): C = Q_c ÷ (3 · 2πf · V²) per phase
  • three phase, wye-connected (each capacitor from line to neutral): C = Q_c ÷ (2πf · V²) per phase, three times the delta value because each sees only V ÷ √3

For the default, 21.1 kVAR at 600 V and 60 Hz is 51.7 µF per phase in delta. Capacitor banks are sold by kVAR rating at a voltage, so the kVAR figure is what you order; the µF figure helps check a nameplate or a meter reading.

Measured readings

If you have a clamp meter reading of volts, amps and kilowatts, choose "Measured" and the calculator finds the power factor directly: PF = kW ÷ (√3 × V × I ÷ 1000) for three phase. 8 kW at 208 V and 30 A is a power factor of 0.740. If the kW is larger than volts times amps allow, a reading is wrong, and the calculator says so.

Why utilities care

Every kVAR of reactive power needs current in the utility's lines and transformers, which heats them and uses capacity without selling any energy. Utilities pass that cost on to larger customers in different ways: billing demand in kVA, a power-factor surcharge, or a rule like Hydro-Québec's, which bills power demand on its domestic, small- and medium-power rates as the higher of real power or 90% of apparent power (95% on large-power rates). At PF 0.80 the default load is billed as 56.25 kW instead of 50 kW, 12.5% more demand charge. Above PF 0.90 the kW figure governs and the penalty disappears.

Canadian supply voltages

Canadian homes have 120/240 V single phase. Commercial and institutional buildings often have 120/208 V three phase, and larger buildings and industry 347/600 V three phase, a Canadian standard (lighting runs at 347 V line-to-neutral). The calculator takes any voltage; enter line-to-line for three phase.

Limits

The calculation assumes sinusoidal voltage and current. Loads with electronic power supplies draw distorted current, whose true power factor is lower than the displacement power factor here, and capacitors on such systems can resonate with the supply. For banks of any size, have an electrician or engineer check harmonics, capacitor voltage rating and switching.

More questions

What is the difference between leading and lagging power factor?

With an inductive load such as a motor or transformer, the current lags behind the voltage and the power factor is called lagging. Capacitive loads make the current lead the voltage. Most industrial plants are lagging, which is why correction uses capacitors; an over-corrected plant at light load can end up leading.

Can a homeowner save money by correcting power factor?

Almost never. Residential customers in Canada and the US are billed on kilowatt-hours, not kVA, so the gadgets sold to 'correct power factor and cut your bill' do not lower a household meter reading. Power factor correction pays off for commercial and industrial customers billed on kVA demand or with a power-factor adjustment.

Where should correction capacitors be installed?

At the motor (individual correction) removes reactive current from the most cable and switches on and off with the load, but needs many small units. A central automatic bank at the main switchboard is cheaper per kVAR and adjusts in steps as the load changes. Many plants combine the two: fixed capacitors on large constant motors and an automatic bank for the rest.

What is the power triangle?

A right triangle with real power P on the horizontal side, reactive power Q on the vertical side and apparent power S as the hypotenuse, so S² = P² + Q². The angle between P and S is the phase angle φ, and its cosine is the power factor. Capacitors shorten the vertical side, which shortens the hypotenuse while P stays the same.

Why do motors have a poor power factor at light load?

A motor needs roughly the same magnetising current, which is reactive, whatever its load. At full load the real current is large compared with it and the power factor is often 0.80 to 0.90; at a quarter load the real current is small and the power factor can drop toward 0.5. Right-sizing motors improves power factor as well as efficiency.

Sources

This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.