Power Factor Calculator: kW, kVA, kVAR and Capacitor Sizing
By FindMySum · Last reviewed
In an AC circuit, not all the current a load draws does useful work. Motors, transformers and fluorescent ballasts also draw reactive current to build their magnetic fields, and that current flows back and forth without delivering energy. Power factor measures how much of the current is doing work. This power factor calculator works out the power triangle for single- and three-phase loads, the line current, and the capacitor bank that brings the power factor up to a target.
The power triangle
Three powers describe an AC load:
- Real power P (kW): the rate at which energy is used, turned into motion, heat or light.
- Reactive power Q (kVAR): energy that sloshes between the supply and the load's magnetic or electric fields every cycle.
- Apparent power S (kVA): the volts times amps the supply must deliver, S² = P² + Q².
Power factor is PF = P ÷ S = cos φ, where φ is the phase angle between voltage and current. The apparent power is:
- single phase: S = V × I
- balanced three phase: S = √3 × V_line-to-line × I
Worked example: the default
The calculator opens with a 50 kW load at PF 0.80 on a 600 V three-phase supply, a typical small Canadian plant.
- S = 50 ÷ 0.80 = 62.5 kVA
- Q = √(62.5² − 50²) = 37.5 kVAR
- φ = acos 0.80 = 36.9°
- Current: 62,500 ÷ (√3 × 600) = 60.1 A
To raise the power factor to 0.95, capacitors must supply part of the reactive power locally:
- tan φ₁ = 37.5 ÷ 50 = 0.750; tan φ₂ = tan(acos 0.95) = 0.329
- Q_c = 50 × (0.750 − 0.329) = 21.1 kVAR
After correction the load draws 52.6 kVA and 50.6 A, almost 16% less current. Real power doesn't change: the motors do the same work.
Capacitor size in microfarads
A capacitor of C farads at voltage V and frequency f supplies Q = 2πf · C · V² vars. So:
- single phase: C = Q_c ÷ (2πf V²)
- three phase, delta-connected (each capacitor across two lines): C = Q_c ÷ (3 · 2πf · V²) per phase
- three phase, wye-connected (each capacitor from line to neutral): C = Q_c ÷ (2πf · V²) per phase, three times the delta value because each sees only V ÷ √3
For the default, 21.1 kVAR at 600 V and 60 Hz is 51.7 µF per phase in delta. Capacitor banks are sold by kVAR rating at a voltage, so the kVAR figure is what you order; the µF figure helps check a nameplate or a meter reading.
Measured readings
If you have a clamp meter reading of volts, amps and kilowatts, choose "Measured" and the calculator finds the power factor directly: PF = kW ÷ (√3 × V × I ÷ 1000) for three phase. 8 kW at 208 V and 30 A is a power factor of 0.740. If the kW is larger than volts times amps allow, a reading is wrong, and the calculator says so.
Why utilities care
Every kVAR of reactive power needs current in the utility's lines and transformers, which heats them and uses capacity without selling any energy. Utilities pass that cost on to larger customers in different ways: billing demand in kVA, a power-factor surcharge, or a rule like Hydro-Québec's, which bills power demand on its domestic, small- and medium-power rates as the higher of real power or 90% of apparent power (95% on large-power rates). At PF 0.80 the default load is billed as 56.25 kW instead of 50 kW, 12.5% more demand charge. Above PF 0.90 the kW figure governs and the penalty disappears.
Canadian supply voltages
Canadian homes have 120/240 V single phase. Commercial and institutional buildings often have 120/208 V three phase, and larger buildings and industry 347/600 V three phase, a Canadian standard (lighting runs at 347 V line-to-neutral). The calculator takes any voltage; enter line-to-line for three phase.
Limits
The calculation assumes sinusoidal voltage and current. Loads with electronic power supplies draw distorted current, whose true power factor is lower than the displacement power factor here, and capacitors on such systems can resonate with the supply. For banks of any size, have an electrician or engineer check harmonics, capacitor voltage rating and switching.
More questions
What is the difference between leading and lagging power factor?
With an inductive load such as a motor or transformer, the current lags behind the voltage and the power factor is called lagging. Capacitive loads make the current lead the voltage. Most industrial plants are lagging, which is why correction uses capacitors; an over-corrected plant at light load can end up leading.
Can a homeowner save money by correcting power factor?
Almost never. Residential customers in Canada and the US are billed on kilowatt-hours, not kVA, so the gadgets sold to 'correct power factor and cut your bill' do not lower a household meter reading. Power factor correction pays off for commercial and industrial customers billed on kVA demand or with a power-factor adjustment.
Where should correction capacitors be installed?
At the motor (individual correction) removes reactive current from the most cable and switches on and off with the load, but needs many small units. A central automatic bank at the main switchboard is cheaper per kVAR and adjusts in steps as the load changes. Many plants combine the two: fixed capacitors on large constant motors and an automatic bank for the rest.
What is the power triangle?
A right triangle with real power P on the horizontal side, reactive power Q on the vertical side and apparent power S as the hypotenuse, so S² = P² + Q². The angle between P and S is the phase angle φ, and its cosine is the power factor. Capacitors shorten the vertical side, which shortens the hypotenuse while P stays the same.
Why do motors have a poor power factor at light load?
A motor needs roughly the same magnetising current, which is reactive, whatever its load. At full load the real current is large compared with it and the power factor is often 0.80 to 0.90; at a quarter load the real current is small and the power factor can drop toward 0.5. Right-sizing motors improves power factor as well as efficiency.