Voltage Drop Calculator: Wire Size, Length and the 3% Rule
By FindMySum · Last reviewed
A voltage drop calculator estimates how many volts are lost in a run of cable between the source and the load, and which wire size keeps that loss within a sensible limit. Every conductor has some resistance, so current flowing through it turns a little of the supply voltage into heat. On short runs the loss is trivial. On long runs, heavy loads or low-voltage systems it can be large enough to dim lights, overheat motors and waste energy. This article walks through the formula, the data behind it, the 3% guideline, and a worked example using the calculator's opening values.
The formula
For a DC circuit or single-phase AC circuit with a resistive load, the drop is:
VD = 2 × L × R × I
L is the one-way length of the run, R is the resistance of one conductor per unit length, and I is the current. The factor of 2 is there because current flows out on one conductor and back on the other, so the total length of copper or aluminum in the loop is twice the distance to the load.
For a balanced three-phase load the drop between lines is:
VD = √3 × L × R × I
The √3 (about 1.732) comes from the 120° phase angle between the lines. The percentage drop is the drop divided by the source voltage, and the voltage at the load is the source voltage minus the drop.
Where the resistance numbers come from
For North American sizes the calculator uses NEC Chapter 9 Table 8, which lists the direct-current resistance of each AWG and kcmil size at 75 °C, per 1,000 feet. It has separate columns for copper and aluminum, and for 14 to 8 AWG it gives both solid and stranded values, because the strands of a stranded conductor twist in a helix, so each strand is slightly longer than the cable and the same cross-section has slightly more resistance. Canadian installations use the same AWG and kcmil sizes.
For metric cable the calculator uses IEC 60228, the international standard for the conductors in insulated cables. It gives the maximum allowed resistance per kilometre at 20 °C for each cross-section from 1.5 mm² upwards. Aluminium conductors in that table start at 10 mm², so smaller aluminium sizes are not offered.
The two tables are published at different temperatures, so the calculator corrects the metric values to the conductor temperature you pick, using the standard linear rule R(T) = R(20 °C) × [1 + α × (T − 20)]. The temperature coefficient α is 0.00393 per °C for annealed copper and 0.00403 per °C for aluminium (IEC 60287-1-1; the NEC Table 8 notes give the same coefficients referred to 75 °C, 0.00323 and 0.00330). The default is 75 °C, the temperature of the AWG table, so a metric and an AWG result describe the same warm, loaded cable: 2.5 mm² copper goes from 7.41 Ω/km at 20 °C to 7.41 × (1 + 0.00393 × 55) ≈ 9.01 Ω/km at 75 °C, 21.6% more. Choose 20 °C to use the IEC values as published, which suits a lightly loaded cable in a cool room. For a 16 A load on 20 m of 2.5 mm² copper at 230 V, the drop is 5.77 V (2.51%) at 75 °C and 4.74 V (2.06%) at 20 °C.
The 3% and 5% guidelines
The NEC's informational notes to sections 210.19(A) and 215.2(A) suggest sizing conductors so that the drop on a branch circuit or a feeder is no more than 3%, and the combined drop from the service to the farthest outlet no more than 5%. In the NEC these notes are advice rather than enforceable requirements, although some jurisdictions and energy codes adopt them. The Canadian Electrical Code makes the same limits a rule (Rule 8-102). The calculator's default limit is 3%; change it if your situation calls for something tighter, such as 2% for sensitive equipment, or if you are checking a feeder against its own share of the 5% total.
Worked example: the calculator's defaults
The calculator opens with 50 ft of 12 AWG stranded copper feeding a 16 A load on a 120 V single-phase circuit, typical of a kitchen or workshop circuit loaded to 80% of a 20 A breaker.
- Resistance from Table 8: 1.98 Ω per 1,000 ft.
- Drop: 2 × 50 × 1.98 × 16 ÷ 1,000 = 3.168 V.
- Percentage: 3.168 ÷ 120 = 2.64%, within the 3% guideline.
- Voltage at the load: 120 − 3.168 = 116.83 V.
- Heat in the cable: 16² × (2 × 50 × 1.98 ÷ 1,000) = 50.7 W, spread along 100 ft of conductor.
The size table under the result repeats the calculation for every gauge. 14 AWG (3.14 Ω per 1,000 ft) would drop 5.02 V, or 4.19%, which is over the limit, so 12 AWG is the smallest size that works for this run. If the same load were 80 ft away, 12 AWG would reach 4.22% and the calculator would recommend 10 AWG.
Voltage drop is not the same as ampacity
A wire has to pass two separate tests. Ampacity asks whether the conductor can carry the current without its insulation overheating; it depends on the insulation's temperature rating, the number of current-carrying conductors bundled together, the ambient temperature and how the cable is installed, and it comes from tables such as NEC 310.16 or the CEC's Tables 1 to 4. Voltage drop asks whether enough voltage reaches the load. On short runs ampacity decides the size; on long runs voltage drop usually does. This calculator answers only the second question, so check the first before choosing a wire.
Limits of the resistive method
The calculation uses DC resistance. That is accurate for DC, for small AC conductors and for resistive loads. For large AC conductors, roughly 1/0 AWG and above, the inductive reactance of the cable adds to the drop, more so in steel conduit than in PVC; NEC Chapter 9 Table 9 gives effective impedance values for those cases. Motor loads also draw several times their running current while starting, so the momentary drop is much larger than the steady figure. Long feeders, motor circuits and anything safety-critical deserve a full calculation by an electrician or engineer, and all wiring has to satisfy the code and the inspector where you live.
More questions
Can I reduce voltage drop by running two smaller wires in parallel?
In principle, two identical conductors in parallel halve the resistance, but the NEC (310.10(G)) and the CEC only allow parallel conductors of 1/0 AWG and larger, all the same length, material and size, with matching terminations. For branch circuits the practical fix is a single larger conductor.
Does a higher voltage circuit have less voltage drop?
The drop in volts depends only on current, length and resistance. A higher voltage carries the same power with less current, so the drop in volts is smaller, and it is a smaller share of a bigger supply voltage. Moving a 2,400 W load from 120 V to 240 V halves the current to 10 A and cuts the percentage drop to a quarter.
How does temperature change the result?
Copper's resistance rises about 0.39% per degree Celsius and aluminum's about 0.40%. The AWG figures here are at 75 °C, a hot conductor near its full rating, so they are conservative for lightly loaded cable. The metric IEC figures are published at 20 °C, so the calculator corrects them to 75 °C by default (copper gains 21.6%), or you can choose 20 °C for a cool, lightly loaded cable.
What voltage should I enter for a 120/240 V split-phase circuit?
Enter the voltage the load actually uses. A 240 V water heater or range runs line to line, so enter 240 V and treat it as single-phase. A 120 V receptacle circuit uses one line and the neutral, so enter 120 V. For a multiwire branch circuit with a balanced load on both halves, the neutral carries little current and the drop is close to half the single-phase figure.
Why does my low-voltage landscape lighting need such large wire?
At 12 V a 3% drop is only 0.36 V, so even a modest current over a long run uses up the budget quickly. A 10 A lighting run of 100 ft on 12 AWG drops about 4 V, a third of the supply. Landscape transformers often have 13, 14 and 15 V taps so the far fixtures still see around 12 V.
Sources