AWG to mm Converter

Convert AWG wire gauge to mm, mm² and inches, or a wire diameter in mm to the nearest AWG, with a full 4/0 to 40 AWG chart and resistance per metre.

Calculator Details

12 AWG diameter:2.0525 mmSee results ↓

AWG to millimetres, or a diameter or area to the nearest AWG

American Wire Gauge; 0000 is also written 4/0. Smaller numbers are thicker.

British wire? SWG to mm converter

SWG (Standard Wire Gauge) sizes differ from AWG: 16 SWG is 1.63 mm, 16 AWG is 1.29 mm.

Your Results

12 AWG diameter: 2.0525 mm

12 AWG diameter

2.0525 mm

0.0808 in · 80.8 mil (ASTM B258)

Cross-section

3.309 mm²

6,530 circular mils (6.53 kcmil)

Nearest metric size (IEC 60228)

4 mm²

Next size up: 4 mm²

Resistance at 20 °C

0.005211 Ω/m copper

0.008542 Ω/m aluminium · nearest SWG 14

12 AWG wire is 2.0525 mm (0.0808 in) in diameter with a cross-section of 3.309 mm² (6,530 circular mils); the nearest metric size is 4 mm².

Detailed Breakdown

AWG wire gauge chart: 4/0 to 40 AWG in mm, inches and mm²
AWGDiameter (mm)Diameter (in)Area (mm²)Ω/m copperΩ/m aluminium
4/0 AWG11.6840.46107.20.00016080.0002636
3/0 AWG10.40490.4096485.030.00020280.0003324
2/0 AWG9.26580.364867.430.00025570.0004192
0 AWG8.25150.3248653.480.00032240.0005285
1 AWG7.34810.289342.410.00040660.0006665
2 AWG6.54370.2576333.630.00051270.0008404
3 AWG5.82730.2294226.670.00064650.00106
4 AWG5.18940.2043121.150.00081520.001336
5 AWG4.62130.1819416.770.0010280.001685
6 AWG4.11540.1620213.30.0012960.002125
7 AWG3.66490.1442910.550.0016340.002679
8 AWG3.26360.128498.3660.0020610.003379
9 AWG2.90640.114426.6340.0025990.00426
10 AWG2.58820.10195.2610.0032770.005372
11 AWG2.30480.090744.1720.0041320.006774
12 AWG (yours)2.05250.080813.3090.0052110.008542
13 AWG1.82780.071962.6240.0065710.01077
14 AWG1.62770.064082.0810.0082860.01358
15 AWG1.44950.057071.650.010450.01713
16 AWG1.29080.050821.3090.013170.0216
17 AWG1.14950.045261.0380.016610.02723
18 AWG1.02370.04030.8230.020950.03434
19 AWG0.91160.035890.65270.026420.0433
20 AWG0.81180.031960.51760.033310.0546
21 AWG0.72290.028460.41050.0420.06885
22 AWG0.64380.025350.32550.052960.08682
23 AWG0.57330.022570.25820.066790.1095
24 AWG0.51060.02010.20470.084220.1381
25 AWG0.45470.01790.16240.10620.1741
26 AWG0.40490.015940.12880.13390.2195
27 AWG0.36060.01420.10210.16890.2768
28 AWG0.32110.012640.080980.21290.349
29 AWG0.28590.011260.064220.26850.4401
30 AWG0.25460.010030.050930.33860.555
31 AWG0.22680.008930.040390.42690.6998
32 AWG0.20190.007950.032030.53830.8825
33 AWG0.17980.007080.02540.67881.113
34 AWG0.16010.00630.020140.8561.403
35 AWG0.14260.005610.015971.0791.769
36 AWG0.1270.0050.012671.3612.231
37 AWG0.11310.004450.010051.7162.813
38 AWG0.10070.003970.0079672.1643.548
39 AWG0.08970.003530.0063182.7294.474
40 AWG0.07990.003140.005013.4415.641

ASTM B258 law, solid round wire. Resistance from resistivity at 20 °C (copper 1/58 Ω·mm²/m, IEC 60028; aluminium 0.028264 Ω·mm²/m, IEC 60889); stranded wire and hotter wire read a little higher. No ampacity: see your electrical code.

How This Calculator Works

How it is calculated

d (mm) = 0.127 × 92^((36 − AWG) ÷ 39) · 0000 = −3, 000 = −2, 00 = −1

AWG = 36 − 39 × log₉₂(d ÷ 0.127) · area = π ÷ 4 × d² · cmil = (d in mils)²

R (Ω/m) = resistivity ÷ area: copper 0.017241, aluminium 0.028264 Ω·mm²/m at 20 °C

Your numbers: 12 AWG: d = 0.127 × 92^((36 − 12) ÷ 39) = 2.0525 mm; area = π ÷ 4 × 2.0525² = 3.309 mm²; copper 0.005211 Ω/m.

Frequently Asked Questions

How do I convert AWG to mm?

Use d = 0.127 mm × 92^((36 − AWG) ÷ 39). For 12 AWG that is 0.127 × 92^(24 ÷ 39) = 2.053 mm; for 14 AWG 1.628 mm and for 10 AWG 2.588 mm. For 0, 00, 000 and 0000 use 0, −1, −2 and −3 as the gauge number. The chart on this page lists every size from 4/0 to 40.

How do I convert mm to AWG?

Reverse the formula: AWG = 36 − 39 × log₉₂(d ÷ 0.127 mm). A 2 mm wire is AWG 12.22, so the nearest size is 12 AWG. Choose “Diameter (mm) → AWG” on the calculator; it also shows the thinnest AWG that is at least as thick, which is the safe choice when replacing wire.

What AWG is 2.5 mm² wire?

2.5 mm² has a diameter of 1.784 mm, which is AWG 13.2: between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). 1.5 mm² is about 15.4 AWG, 4 mm² about 11.2 AWG and 6 mm² about 9.4 AWG. Metric and AWG sizes never line up exactly.

Why do smaller AWG numbers mean thicker wire?

The gauge number originally counted how many times the wire had been drawn through a die. Each pass made it thinner, so a higher number is a thinner wire. Every 6 gauges halves the diameter, and every 3 gauges roughly halves the area.

What is a circular mil?

The area of a circle one thousandth of an inch (one mil) across, used in North America for wire areas: the area in circular mils is simply the diameter in mils squared. 12 AWG (80.8 mil) is about 6,530 circular mils. Large cables are sized in kcmil (thousands of circular mils), such as 250 kcmil.

How much current can 12 AWG copper wire carry?

It depends on the insulation temperature rating, the installation and the code, so this converter does not give a figure. In houses, 12 AWG copper is typically protected at 20 A under both the Canadian Electrical Code and the NEC, but check the ampacity tables (CEC Table 2, NEC 310.16) and your inspector.

Is AWG the same as SWG?

No. AWG (American Wire Gauge, also called Brown & Sharpe) follows a geometric formula; SWG (British Standard Wire Gauge) is a table of fixed sizes. The same number is a different wire: 16 AWG is 1.29 mm, 16 SWG is 1.63 mm. Use the SWG to mm converter for British gauges.

What is the resistance of 14 AWG copper wire?

About 0.00829 Ω per metre (8.29 Ω per km) at 20 °C for solid copper, from its resistivity of 1/58 Ω·mm²/m and its 2.08 mm² area. Stranded wire and warmer wire read slightly higher; the voltage drop calculator uses the NEC values at 75 °C.

AWG diameters follow the ASTM B258-18 (reapproved 2026) law d = 0.005 in × 92^((36 − n) ÷ 39) for solid round wire, 0000 (4/0) to 40 AWG; areas are π ÷ 4 × d². Metric sizes are the IEC 60228:2023 nominal areas. Resistance per metre is for a solid conductor at 20 °C from resistivity (copper 1/58 Ω·mm²/m, IEC 60028; aluminium 0.028264 Ω·mm²/m, IEC 60889); stranded conductors and the NEC Chapter 9 Table 8 values at 75 °C used by the voltage drop calculator are higher. Not included: ampacity (allowable current), which depends on insulation, temperature and installation and comes from the Canadian Electrical Code Table 2 or NEC Table 310.16, not from the gauge; insulation thickness; and stranded overall diameters. This is not a design: your electrical code and inspector govern.

AWG to mm Converter: American Wire Gauge in mm, mm² and Inches

By FindMySum · Last reviewed

American Wire Gauge (AWG) is the size system for electrical wire in Canada and the United States, while most of the world describes wire by its cross-section in square millimetres. This converter goes both ways: choose an AWG size to get its diameter in millimetres and inches, its area in mm² and circular mils, the nearest metric cable size and its resistance per metre; or enter a diameter or area in millimetres to find the nearest AWG. A full chart from 4/0 to 40 AWG sits below the calculator, with one row per gauge you can link to directly.

The AWG formula

AWG is defined by a geometric progression in ASTM B258. Size 36 is exactly 0.005 inch (0.127 mm) across and size 0000 is exactly 0.46 inch, and there are 39 steps between them, so each step changes the diameter by the 39th root of 92 (about 1.123):

d (mm) = 0.127 × 92^((36 − n) ÷ 39)

For the sizes thicker than 0, the gauge number n is −1 for 00 (2/0), −2 for 000 (3/0) and −3 for 0000 (4/0). Two rules of thumb follow from the formula: every 6 gauges halves (or doubles) the diameter, and every 3 gauges roughly halves (or doubles) the area and so doubles (or halves) the resistance.

Worked example: 12 AWG

The calculator opens at 12 AWG, the common size for 20-amp household circuits in North America:

d = 0.127 × 92^(24 ÷ 39) = 2.0525 mm (0.0808 in)

The cross-section is π ÷ 4 × 2.0525² = 3.309 mm², or 80.8² ≈ 6,530 circular mils. The nearest IEC metric size on a logarithmic scale is 4 mm²; 2.5 mm² is smaller, so a metric equivalent that is never undersized is also 4 mm². Solid copper of that area has a resistance of about 0.00521 Ω per metre at 20 °C.

mm to AWG

Reversing the formula gives the gauge of any diameter:

AWG = 36 − 39 × log₉₂(d ÷ 0.127 mm)

A 2 mm wire comes out at AWG 12.22, so the nearest size is 12 AWG. A 2.5 mm² metric conductor is 1.784 mm across, AWG 13.21, between 14 AWG and 12 AWG; the calculator shows the nearest size (13 AWG) and the thinnest size that is at least as large. When matching a metric cable to an AWG rating, always round to the thicker wire.

Circular mils and kcmil

North American codes often give areas in circular mils: the square of the diameter in thousandths of an inch. It avoids the π in the circle area, so 12 AWG at 80.8 mil is about 6,530 cmil. Above 4/0, cables are named by their area in thousands of circular mils: 250 kcmil, 500 kcmil and so on. One kcmil is about 0.5067 mm².

Resistance per metre

The chart and the calculator give the DC resistance of a solid round conductor at 20 °C, worked out from the resistivity of annealed copper (1/58 Ω·mm²/m, the International Annealed Copper Standard of IEC 60028) and of hard-drawn aluminium (0.028264 Ω·mm²/m, IEC 60889), the same basis as the metric cable standard IEC 60228. Resistance rises about 0.4% per degree Celsius, so the figures used for voltage-drop design at a conductor temperature of 75 °C are around 20% higher. The voltage drop calculator uses those code values.

What gauge does not tell you

The gauge only describes the conductor's size. How much current a wire may carry (its ampacity) depends on the insulation's temperature rating, how many conductors share a cable or conduit, the ambient temperature and the installation method, and it is set by the Canadian Electrical Code (Table 2) or the NEC (Table 310.16), not by a conversion. This page deliberately gives no current ratings. For sizing a circuit by voltage drop use the voltage drop calculator, for how many conductors fit in a box the box fill calculator, and for British gauges the SWG to mm converter. This page is not a design: your electrical code and inspector govern.

More questions

Why is 4/0 AWG written that way?

Sizes thicker than 0 AWG are written with extra zeros: 00, 000 and 0000, shortened to 2/0, 3/0 and 4/0 and spoken as "two-aught", "three-aught" and "four-aught". In the formula they count as −1, −2 and −3. Beyond 4/0 (11.68 mm, 107 mm²) North American cables are sized in kcmil instead.

Does stranded wire of the same AWG have the same diameter?

No. A stranded conductor of a given AWG has about the same copper area as the solid wire, but the gaps between strands make it a few percent wider overall. Its resistance is also slightly higher. The AWG number refers to the area, so use the area, not a caliper reading, for stranded wire.

What AWG is 1 mm diameter wire?

A 1 mm wire is AWG 18.2, so the nearest standard size is 18 AWG (1.024 mm). For a replacement that is never thinner than the original, the converter also shows the thinnest AWG at least as thick, which for 1 mm is 18 AWG.

Why do Canadian and US codes size wire in AWG while Europe uses mm²?

North America standardised on the Brown & Sharpe gauge in the 19th century, and the CEC and NEC tables are written in AWG and kcmil. Most other countries adopted the metric IEC 60228 sizes (1.5, 2.5, 4, 6 mm²…). Equipment sold internationally often lists both.

How accurate is the AWG formula?

It is the definition. ASTM B258 defines the sizes by the formula and then rounds the nominal diameter to 0.1 mil (0.0025 mm) for its tables, so a spec sheet may show 2.052 mm for 12 AWG where the formula gives 2.0525 mm. Manufacturing tolerances are far larger than that rounding.