Friction Loss Calculator

Pipe friction loss by Darcy–Weisbach (Colebrook), Hazen–Williams or fire-hose coefficients, plus fittings and elevation, in kPa, psi and metres or feet of head.

Calculator Details

Total pressure loss:22.31 kPa (3.236 psi)See results ↓

Darcy–Weisbach works for any water temperature and pipe; Hazen–Williams is the waterworks and sprinkler formula; fire hose uses fire-service coefficients

L/s, mm and m, or US gpm, inches and feet (fire hose is always gpm and ft)

Water flowing through the pipe (L/s metric, US gpm imperial)

Actual bore (mm or in), not the nominal size

Length of straight pipe (m or ft)

Sets the wall roughness for Darcy–Weisbach

Sets the water’s density and viscosity, 0–100 °C (cold mains water is about 10–15 °C)

Sum of loss coefficients for elbows, valves, tees and entrances (0 to leave out)

Height the water is lifted from start to end (negative if it drops)

Your Results

Total pressure loss: 22.31 kPa (3.236 psi)

Total pressure loss

22.31 kPa (3.236 psi)

Total head

2.277 m

7.47 ft of water

Friction alone

22.31 kPa

2.277 m of head per 100 m

Velocity and flow

1.02 m/s

Re 44,729, turbulent

Friction factor f

0.02152

Swamee–Jain check: 0.02141

2 L/s through 100 m of pvc or plastic (drawn) pipe loses 22.3 kPa (3.24 psi) to friction; with fittings and lift the total is 22.3 kPa, 2.28 m of head.

Compare scenarios

Save these inputs as a scenario, change them, and compare the results side by side.

Loading, available in a moment

Loss by flow rate

Loss by flow rate

Detailed Breakdown

Where the pressure goes
PartHead (m)Head (ft)kPapsi
Pipe friction2.2777.4722.313.236
Total2.2777.4722.313.236
Loss at other flow rates (without elevation)
Flow (L/s)kPapsi
000
0.41.3210.1916
0.84.4230.6415
1.29.0261.309
1.615.012.177
2 (you)22.313.236
2.430.864.477
2.840.645.894
3.251.67.484
3.663.729.242
476.9811.17

How This Calculator Works

How It’s Calculated

h_f = f × (L ÷ D) × v² ÷ 2g · 1/√f = −2 log₁₀(ε/3.7D + 2.51/(Re√f)) · h_m = ΣK × v² ÷ 2g

Your calculation: the water moves at 1.019 m/s (Re 44,729, turbulent), giving a friction factor of 0.02152. Friction costs 22.31 kPa over 100 m; with fittings and elevation the total is 2.277 m of head, 22.31 kPa or 3.236 psi.

Frequently Asked Questions

What is friction loss in a pipe?

The pressure a moving fluid loses rubbing against the pipe wall and itself. It is usually given as head (metres or feet of water) or pressure. The default, 2 L/s of 15 °C water through 100 m of 50 mm PVC, loses 22.3 kPa (3.24 psi).

How does flow rate change friction loss?

Roughly with the square of the flow in turbulent pipes. Doubling the default flow to 4 L/s raises the loss from 22.3 to 77 kPa, about 3.5 times, a little less than 4 because the friction factor falls as Re rises.

How much does a bigger pipe help?

A lot: friction loss falls with about the fifth power of the diameter at the same flow. Going from a 50 mm to a 63 mm bore cuts the default loss from 22.3 kPa to 7.39 kPa.

Darcy–Weisbach or Hazen–Williams?

Darcy–Weisbach is the general physical formula: it works for any temperature, flow regime and pipe roughness. Hazen–Williams is an empirical formula for ordinary-temperature water in turbulent flow, used by waterworks and in sprinkler design (NFPA 13). For cold water in normal pipes they agree within a few per cent.

What C factor should I use?

The NFPA 13 table gives 150 for plastic and copper, 140 for cement-lined ductile iron, 120 for black or galvanized steel in wet sprinkler systems and 100 for dry systems and unlined cast iron. Old, tuberculated pipe can drop well below 100.

How do fire departments calculate hose friction loss?

With FL = C × Q² × L, where Q is the flow in hundreds of gpm and L the length in hundreds of feet. The IFSTA coefficient for 1¾″ hose is 15.5, so 150 gpm through 200 ft loses 69.75 psi; for 2½″ hose it is 2.

What is a minor loss coefficient (K)?

Each fitting, valve, bend and entrance loses about K × v²/2g of head, with K from the fitting maker or a hydraulics handbook. Add the K values of every fitting in the run and enter the total as ΣK. A sharp pipe entrance is about 0.5 and an exit into a tank 1.0.

For clean water flowing full in a round pipe. Darcy–Weisbach uses the Colebrook–White friction factor (64/Re when laminar; the turbulent value through the 2,300–4,000 transition) with water properties from the NIST WebBook. Roughness values are for new pipe, Hazen–Williams C factors follow the NFPA 13 table and fire-hose coefficients are the IFSTA values; all three tables come from published reproductions and are awaiting review against the standards themselves. Fittings are entered as a total ΣK; pipe ageing, scale, air pockets, other liquids and pump curves aren’t modelled. Real fire hose varies by brand and condition: flow-test your own lines.

Friction Loss Calculator: Darcy–Weisbach, Hazen–Williams and Fire Hose

By FindMySum · Last reviewed

Water loses pressure as it flows, through rubbing on the pipe wall, through turbulence in fittings, and by climbing. This friction loss calculator works out how much, three ways: the general Darcy–Weisbach equation with the Colebrook friction factor, the Hazen–Williams formula used for water mains and sprinkler systems, and the fire-service formula for hose lines. It adds fitting losses and elevation and gives the answer as head and as pressure in kPa and psi.

Head and pressure

Engineers often express a pressure loss as head, the height of a water column that would produce it. The two are linked by Δp = ρ × g × h: for water, 1 m of head is about 9.8 kPa, and 1 ft about 0.433 psi. Pumps are rated in head, so working in metres or feet makes pump selection easier.

Darcy–Weisbach

The physical formula for friction in a full pipe:

h_f = f × (L ÷ D) × v² ÷ 2g

L is the pipe length, D the inside diameter, v the average velocity and f the Darcy friction factor. In laminar flow (Reynolds number below about 2,300), f = 64 ÷ Re exactly. In turbulent flow it depends on Re and on the relative roughness ε ÷ D, through the Colebrook–White equation:

1 ÷ √f = −2 log₁₀(ε ÷ 3.7D + 2.51 ÷ (Re √f))

The equation has f on both sides, so the calculator solves it by iteration and also shows the Swamee–Jain explicit approximation as a check, which usually agrees within about 1%. Water's density and viscosity come from the NIST tables at the temperature you give.

Worked example: the default

2 L/s of water at 15 °C through 100 m of 50 mm-bore PVC:

  • Velocity: 0.002 ÷ (π × 0.025²) = 1.02 m/s
  • Reynolds number: 999.1 × 1.02 × 0.05 ÷ 0.0011376 ≈ 44,700 (turbulent)
  • Relative roughness: 0.0015 mm ÷ 50 mm = 0.00003, so f ≈ 0.0215
  • h_f = 0.0215 × (100 ÷ 0.05) × 1.02² ÷ (2 × 9.807) ≈ 2.28 m

That is about 22.3 kPa or 3.2 psi of pressure lost. Doubling the flow roughly quadruples the loss, and a 63 mm pipe instead of 50 mm cuts it to about a third.

Hazen–Williams

An empirical formula that has been used for water distribution for over a century. In SI units:

h_f = 10.67 × L × Q^1.852 ÷ (C^1.852 × D^4.8704)

with Q in m³/s, L and D in metres. In US sprinkler work, NFPA 13 writes it as p = 4.52 Q^1.85 ÷ (C^1.85 d^4.87) psi per foot, with Q in gpm and d in inches; the two forms agree closely. C is a smoothness coefficient: 150 for plastic and copper, 140 for cement-lined ductile iron, 120 for wet steel sprinkler pipe and 100 for unlined iron or dry steel systems. The formula is only meant for water near normal temperatures in turbulent flow.

Minor losses and elevation

Fittings, valves, bends and entrances each lose K × v² ÷ 2g of head. Add up the K values for the fittings in your run and enter the total. Elevation is simpler: lifting water 10 m costs 10 m of head, about 98 kPa, whatever the pipe. A negative elevation (water flowing downhill) gains pressure.

Fire hose friction loss

Fire departments use a quick form calibrated for hose:

FL = C × Q² × L

where FL is in psi, Q is the flow in hundreds of US gallons per minute and L the length in hundreds of feet. The coefficients are the standard IFSTA values: 24 for 1½″, 15.5 for 1¾″, 2 for 2½″, 0.8 for 3″ with 2½″ couplings, 0.2 for 4″ and 0.08 for 5″ supply hose.

Worked example: a 1¾″ attack line

150 gpm through 200 ft of 1¾″ hose: FL = 15.5 × 1.5² × 2 = 69.75 psi. The pump operator adds the nozzle pressure, any appliance losses and about 0.5 psi per foot of elevation (the fire-service rule) to get the pump discharge pressure. Modern hose linings often perform better than these coefficients, so many departments flow-test their own lines and use their own numbers.

Accuracy

Pipe roughness values are for new, clean pipe and carry a large uncertainty, often ±30% or more; old steel and cast iron can be several times rougher. Losses also depend on joint quality, partly closed valves and trapped air. Treat the result as a design estimate and leave a margin when sizing a pump.

To check whether the flow is laminar or turbulent, use the Reynolds number calculator. The flow rate calculator converts between velocity and flow, and the pressure calculator gives the static pressure of a water column.

More questions

Why is my shower weak upstairs but fine downstairs?

Two losses stack up. Lifting water one storey, about 3 m, costs roughly 30 kPa (4.3 psi) of pressure, and the longer, narrower pipe run to the upper floor adds friction, especially when other taps are open and the flow in shared pipes rises. Larger supply lines or a home-run manifold reduce the friction part.

Does hot water have more or less friction loss than cold?

Slightly less in the same pipe at the same flow. Hot water is less viscous, so the Reynolds number is higher and the friction factor a little lower. The Darcy–Weisbach option picks this up from the water temperature; Hazen–Williams can't, which is one reason it's limited to ordinary temperatures.

How do I size a pump with this?

Add up the total head the pump has to supply: the vertical lift, the friction and fitting losses at the design flow, and any pressure needed at the outlet. Then choose a pump whose curve delivers that head at that flow, ideally near its best-efficiency point. The flow table on the page gives the system curve to compare against.

What is velocity head?

The kinetic energy of the flow written as a height, v² ÷ 2g. Water at 2 m/s has a velocity head of about 0.2 m. Minor-loss coefficients are multiples of it, which is why fittings matter more in fast-flowing systems.

What happens to friction loss in two hose lines side by side?

Splitting a flow between two equal lines halves the flow in each, and because loss goes with the square of the flow, each line loses about a quarter as much. That's the idea behind siamesed supply lines, which the fire service treats with its own reduced coefficient.

Sources

This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.