Heat Transfer Calculator

Heat loss through walls, ceilings and insulated pipes: thermal resistance (RSI and R-value), U-value, conduction and convection, with NBC 9.36 minimums.

Calculator Details

Heat loss:107.3 WSee results ↓

Heat loss through a wall, ceiling or floor; through an insulated pipe; or by convection or thermal radiation from a surface

Area of the wall, ceiling, floor or surface

Room air, or the fluid inside the pipe

Outdoor air, or the air around the pipe

°C or °F

Sets the inside air film and the NBC 9.36.2.6 minimum to compare with

mm or inches, for layers and pipe sizes

Layers from inside to outside; choose None to leave a layer out

Thickness of layer 1 (drywall by default)

Choose None to leave this layer out

Thickness of layer 2 (a 2×6 cavity by default)

Choose None to leave this layer out

Thickness of layer 3 (sheathing by default)

Choose None to leave this layer out

The layer whose insulation is interrupted by wood framing (parallel-path method)

23% for studs at 406 mm (16 in) on centre, 20% at 610 mm (24 in) (NRCan / NBC)

The still-air layers on each surface (NRCan Table CM-1); turn off for a bare slab or rod

By heating degree-days: 4 under 3,000 (Vancouver), 5 (Toronto), 6 (Ottawa, Montréal), 7A (Edmonton), 7B (Fort McMurray), 8 (7,000 and over, the North)

NBC allows slightly lower wall and ceiling values with an HRV (Table 9.36.2.6.-B)

Fuel that makes up the lost heat

Sets the default fuel price and currency

Hours of heat loss to total (24 = one day; 5,000 ≈ a heating season)

From your bill; 0 uses the default for your province or state

0 uses the typical efficiency for the fuel (e.g. 92% for a gas furnace)

Your Results

Heat loss: 107.3 W

Heat loss

107.3 W

366.2 Btu/h for 31 K difference

Effective thermal resistance

RSI 2.888

R-16.4 (ft²·°F·h/Btu)

U-value

0.3462 W/(m²·K)

0.06098 Btu/(h·ft²·°F)

NBC minimum, zone 6

RSI 3.08

Below the prescriptive minimum

Heat cost over 2.576 kWh

$0.11

Natural gas at $0.40/m³, 92% efficient

The assembly has an effective RSI of 2.888 (R-16.4) and loses 107.3 W (366.2 Btu/h), about $0.11 of heat over the period; it falls short of the NBC zone 6 minimum of RSI 3.08.

Compare scenarios

Save these inputs as a scenario, change them, and compare the results side by side.

Loading, available in a moment

Thermal resistance by layer

Thermal resistance by layer

Detailed Breakdown

Layer by layer, warm side to cold side
LayerThickness (mm)RSITemperature drop (K)Cold-side temperature (°C)
Inside air film—0.121.28819.71
Gypsum board (drywall)12.70.080010.858818.85
Glass-fibre batt R-22 (RSI 3.87 in 140 mm) between 23% wood framing1402.54927.36−8.51
Oriented strand board (OSB)11.10.10881.168−9.678
Outside air film—0.030.322−10

The insulation takes most of the temperature drop; where it drops below the dew point of indoor air, moisture can condense, which is why the vapour barrier goes on the warm side.

NBC 9.36.2.6 minimum effective RSI: above-ground wall
Climate zoneWithout HRVWith HRV
Zone 42.782.78
Zone 53.082.97
Zone 6 (yours)3.082.97
Zone 7A3.082.97
Zone 7B3.853.08
Zone 83.853.08

Prescriptive path of the National Building Code (as published in BCBC 2018); provinces and cities may adopt different tiers.

How This Calculator Works

How It’s Calculated

Layer: RSI = thickness ÷ k · Framed layer: RSI = 100 ÷ (%frame ÷ RSI_frame + %cavity ÷ RSI_cavity)
Total RSI = films + ΣRSI · U = 1 ÷ RSI · Heat loss = U × A × ΔT
Pipe: P = ΔT ÷ (ln(r₂/r₁) ÷ 2πkL + 1 ÷ h·2πr₂L) · Convection: P = hAΔT
Radiation: P = εσA(T_s⁴ − T_surr⁴), T in kelvin, σ = 5.670 374 419 × 10⁻⁸ W/(m²·K⁴)

Your calculation: the layers add up to RSI 2.888 (R-16.4), so U = 0.3462 W/(m²·K) and 10 m² with a 31 K difference loses 107.3 W. Over 24 hours that is 2.576 kWh of heat.

Steady state: temperatures held constant, no sun, wind-washing or air leakage. Real heat loss through a whole house also includes windows, air leakage and the foundation.

Frequently Asked Questions

What is the difference between RSI and R-value?

Both measure thermal resistance. RSI is metric, in m²·K/W; the R-value on North American insulation labels is imperial, in ft²·°F·h/Btu. 1 R = 0.17611 RSI and 1 RSI = R-5.678: multiply RSI by about 5.68 to get R. A batt sold as R-20 is RSI 3.52. Canadian codes use RSI.

What is a U-value?

The rate of heat flow through one square metre for each degree of temperature difference, in W/(m²·K): the reciprocal of the total RSI. The default 2×6 wall has U = 0.346, so 10 m² with 31 °C between inside and out loses 107 W. Windows are usually rated by U-value, walls and roofs by RSI.

Why is a wall’s effective RSI lower than its insulation’s?

Wood studs conduct heat about four times better than batts, and they cover roughly 23% of a wall framed at 406 mm (16 in) on centre. Heat takes the easy path through the studs (thermal bridging). R-22 batts are RSI 3.87, but the framed layer is only about RSI 2.55; without framing the whole wall would be RSI 4.21 instead of 2.89.

How do I meet the NBC wall requirement?

The National Building Code’s prescriptive path sets a minimum effective RSI by climate zone: 3.08 for walls in zone 6 without a heat-recovery ventilator, 2.97 with one. A 2×6 wall with R-22 batts reaches about 2.89, so most builders add continuous exterior insulation: 50 mm of XPS brings it to 4.64, which also breaks the thermal bridge through the studs.

What are air films?

Thin layers of still air cling to every surface and add a little resistance: NRCan uses RSI 0.12 inside a wall, 0.11 under a ceiling (heat flowing up), 0.16 above a floor (heat flowing down) and 0.03 outside in winter wind. They are counted in the code’s effective RSI.

How much heat does pipe insulation save?

A lot. A 2-inch steel pipe carrying 80 °C water through 20 °C air loses about 1,140 W per 10 m bare, but only 203 W with 25 mm of mineral wool, and the insulation surface stays near 25.9 °C. The calculator ignores the pipe wall and the inside film, which add little resistance.

What is thermal conductivity?

A material property, k, in W/(m·K): the heat flow through a 1 m cube of the material with 1 K between opposite faces. Insulation is around 0.03–0.04, wood about 0.12, concrete 2.5, steel 80 and copper 390. A layer’s resistance is its thickness divided by k.

Can I use this to size a furnace?

Not on its own. A heating system is sized from the whole house’s heat loss at the local design temperature, including windows, doors, air leakage, ventilation and the foundation (CSA F280 in Canada, ACCA Manual J in the US). This calculator gives the conduction loss of one assembly, which is one part of that calculation.

Steady-state conduction, convection and radiation (OpenStax University Physics Vol. 2 §1.6; σ from CODATA 2022) with NRCan Table CM-1 material and air-film values and the parallel-path method for framed layers; NBC 9.36.2.6 minimums are the prescriptive values as published in BCBC 2018 (NBC 2020 confirmation pending). Fuel prices are defaults: enter your own. Radiation assumes large surroundings at one temperature (no view factors). It leaves out windows and doors, air leakage, thermal bridges other than wood framing (steel studs, slab edges, balconies), moisture, solar gain, heat stored in mass, the pipe wall and inside film, and the whole-house heat-loss calculation used to size heating (CSA F280).

Heat Transfer Calculator: Wall RSI, R-Value, U-Value and Heat Loss

By FindMySum · Last reviewed

Heat always flows from warm to cold, and how fast it gets through a wall, a roof or a pipe depends on the materials in the way. This heat transfer calculator adds up the thermal resistance of each layer of a wall, ceiling or floor, including the wood framing and the still-air films on each side, and turns it into an effective RSI and R-value, a U-value, the heat loss in watts and Btu per hour, and what that heat costs with your fuel. It also handles insulated pipes and simple convection, and compares building assemblies with the minimum effective RSI in Canada's National Building Code.

Conduction and thermal resistance

Heat conducts through a slab of material at a rate

  • P = kAΔT ÷ d

where k is the material's thermal conductivity, A the area, ΔT the temperature difference and d the thickness. Builders flip this around and describe each layer by its thermal resistance, RSI = d ÷ k, in m²·K/W. Resistances in series simply add, like resistors in a circuit:

  • total RSI = inside air film + each layer + outside air film
  • U = 1 ÷ total RSI, and heat loss = U × A × ΔT

The calculator's material values come from Natural Resources Canada's tables (Table CM-1), the same ones used to show compliance with the National Building Code, with metals and glass from the OpenStax physics text.

Framing: the thermal bridge

In a wood-frame wall, the batts sit between studs, and the studs conduct heat much better than the insulation. At 406 mm (16 in) on centre, framing covers about 23% of the wall. Heat flows through the studs and the insulation side by side, so the effective resistance of that layer is

  • RSI_effective = 100 ÷ (%framing ÷ RSI_wood + %cavity ÷ RSI_insulation)

For a 2×6 wall with R-22 batts (RSI 3.87) and 140 mm spruce studs (RSI 1.19), the framed layer works out to RSI 2.55, matching NRCan's published table. The insulation alone would suggest 3.87, a difference of a third.

Worked example: a 2×6 wall in Ottawa

The calculator opens with 10 m² of a typical wall: 12.7 mm drywall, R-22 batts in a 2×6 frame, 11.1 mm OSB sheathing, and air films on both sides, with 21 °C inside and −10 °C outside.

LayerRSI
Inside air film0.12
Gypsum board, 12.7 mm0.080
R-22 batts between 23% framing2.549
OSB, 11.1 mm0.109
Outside air film0.03
Total2.888 (R-16.4)
  • U = 1 ÷ 2.888 = 0.346 W/(m²·K)
  • heat loss = 0.346 × 10 × 31 = 107 W, or 366 Btu/h

Over a day that is 2.6 kWh of heat. Ottawa is in NBC climate zone 6, where the prescriptive minimum for walls is RSI 3.08 without a heat-recovery ventilator and 2.97 with one, so this wall falls a little short. Adding 50 mm of exterior XPS (RSI 1.75) lifts it to 4.64 and cuts the loss to 67 W.

The National Building Code minimums

Section 9.36 of the National Building Code of Canada sets the minimum effective RSI of walls, ceilings and floors for houses and small buildings by climate zone, based on heating degree-days. A house with a heat-recovery ventilator may use slightly lower values for walls and ceilings. The calculator shows the full table for the assembly you choose. Provinces and cities adopt the code on their own schedules and some, like British Columbia's Step Code and Ontario's SB-12, add their own paths, so check your local rules.

Insulated pipes

Around a pipe, the heat spreads out through a growing area, so the resistance of a cylindrical layer is ln(r₂/r₁) ÷ (2πkL) rather than d ÷ k. Add the convection resistance of the outside air, 1 ÷ (h × 2πr₂L), and the heat loss is ΔT divided by the sum. A 2-inch steel pipe carrying 80 °C water through a 20 °C room loses about 1,140 W per 10 m bare and about 200 W with 25 mm of mineral wool: an 82% saving.

Convection

Heat leaving a surface into moving air or water follows P = hAΔT, where h, the convection coefficient, depends on the fluid and how fast it moves: around 5 to 10 W/(m²·K) in still air, 10 to 25 in a breeze, and hundreds to thousands for flowing water. The calculator's convection mode is useful for radiators, tanks and cooling surfaces.

Radiation

Every surface also gives off heat as infrared light. The radiation mode uses the Stefan–Boltzmann law for a surface in large surroundings: P = εσA(T_s⁴ − T_surr⁴), with both temperatures in kelvin, σ = 5.670 374 419 × 10⁻⁸ W/(m²·K⁴) and ε the emissivity, about 0.9 for paint, brick and wood and well under 0.1 for polished metal. A painted surface at 21 °C facing surroundings at −10 °C radiates a net 137 W per square metre, so radiation matters as much as convection near room temperature. The page also gives the linearised radiation coefficient h_r = εσ(T_s² + T_surr²)(T_s + T_surr), which can be added to a convection coefficient to get a combined surface coefficient.

The cost of the heat

The calculator multiplies the heat loss by the number of hours you choose to get kWh, converts that to fuel with the energy content and typical efficiency of natural gas, heating oil, propane or electric heat, and prices it with a default for your province or state or the price on your bill. Use about 5,000 hours and an average winter temperature difference for a rough seasonal figure.

Limits

This is steady-state conduction through opaque assemblies. Real buildings also lose heat through windows and doors, air leakage and the foundation, and gain heat from the sun and from people and appliances. The radiation mode treats the surroundings as large and at one temperature; for a star, a filament or a black body's spectrum, use the Stefan–Boltzmann calculator. For sizing a furnace or heat pump, a whole-house heat-loss calculation such as CSA F280 is the right tool.

More questions

Is a higher RSI always better?

For keeping heat in, yes, but with diminishing returns. Heat loss is proportional to 1/RSI, so going from RSI 2 to RSI 4 halves the loss through that wall, while going from RSI 4 to RSI 6 saves only another third of what is left. Once walls and ceilings are well insulated, windows and air leakage usually dominate the heat loss.

Where should the vapour barrier go?

On the warm side of the insulation in a Canadian heating climate, usually just behind the drywall. The layer table shows why: the temperature falls steeply through the insulation, and indoor moisture that reaches a cold surface inside the wall can condense. Exterior insulation keeps the sheathing warmer, which reduces that risk.

Why do steel studs perform so badly?

Steel conducts heat about 500 times better than wood. Steel studs short-circuit cavity insulation so strongly that the parallel-path method used here overestimates their walls; codes use special correction factors for them, and they usually need continuous exterior insulation to meet energy rules.

What is a heating degree-day?

A measure of how cold a place is over a year: for each day, the number of degrees the average temperature falls below 18 °C, added up over the year. Vancouver has about 2,800, Toronto about 3,500, Ottawa about 4,500 and Yellowknife over 8,000. The National Building Code groups locations into climate zones by this number.

How do I turn the heat loss into a yearly cost?

Multiply the U-value and area by the heating degree-days and 24 hours: kWh per year ≈ U × A × HDD × 24 ÷ 1,000. Then price that energy with your fuel and its efficiency. Entering the average winter temperature difference and about 5,000 heating hours in the calculator gives a similar estimate.

Does insulation work in summer too?

Yes. Conduction runs in whichever direction the temperature difference points, so the same RSI slows heat coming in on a hot day. In summer, solar heat on roofs and through windows matters more, and attic ventilation and shading do much of the work.

Sources

This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.

Spotted a wrong result or a bug? Report a problem