Transformer Sizing Calculator

Size a single- or three-phase transformer: load kVA, the next standard kVA rating, full-load current on both sides, turns ratio and reflected impedance.

Calculator Details

Standard transformer size:75 kVASee results ↓

Single-phase (homes, small loads) or three-phase (commercial and industrial)

Apparent power (kVA), real power (kW) and power factor, or the secondary current

Supply side; line-to-line for three-phase (600 V is common in Canadian commercial buildings, 480 V in the US)

Load side; line-to-line for three-phase (208 V for a 120/208 V panel)

Total connected or calculated demand load in kilovolt-amperes

cos φ of the load: about 0.8–0.9 for motors, 1 for heaters

Spare capacity for future load (25% is a common design practice, not a code rule)

Full-load efficiency; distribution transformers are typically 97–99%

If you are winding or checking a transformer: the calculator gives the secondary turns; 0 to skip

Your Results

Standard transformer size: 75 kVA

Standard transformer size

75 kVA

Three-phase, next size at or above 50 kVA

Full-load current, primary

72.169 A

Your load draws 38.49 A

Full-load current, secondary

208.18 A

Your load draws 111.03 A

Turns ratio Np : Ns

2.8846 : 1

Step-down

Load on this rating

53.3%

40 kVA now, 50 kVA with the margin

A 40 kVA load plus margin needs 50 kVA, so the next standard three-phase size is 75 kVA, with full-load currents of 72.17 A primary and 208.2 A secondary.

Compare scenarios

Save these inputs as a scenario, change them, and compare the results side by side.

Loading, available in a moment

Detailed Breakdown

Standard sizes around your load
Rating (kVA)Primary FLA (A)Secondary FLA (A)Your load
3028.86883.272133%
4543.301124.9188.9%
75 (chosen)72.169208.1853.3%
112.5108.25312.2735.6%
150144.34416.3626.7%
225216.51624.5417.8%

Full-load current (FLA) is the rated kVA divided by the voltage (and by √3 for three-phase). Sizes from manufacturer catalogues; check availability for your voltages.

How This Calculator Works

How It’s Calculated

Load: S = √3 × V × I = kW ÷ PF
Required = S × (1 + margin) → next standard kVA
FLA = kVA × 1000 ÷ (√3 × V) · Vp ÷ Vs = Np ÷ Ns = Is ÷ Ip

Your calculation: the load is 40 kVA (36 kW). With a 25% margin it needs 50 kVA, so the next standard size is 75 kVA. Its full-load current is 72.169 A at 600 V and 208.18 A at 208 V; the turns ratio is 2.8846 : 1, and a 1.0816 Ω per-phase load looks like 9 Ω from the primary.

Overcurrent protection, conductors and grounding are not sized here: a licensed electrician or engineer sizes them under CSA C22.1:24 Canadian Electrical Code, Part I, Section 26 or NFPA 70 National Electrical Code, Article 450.

Frequently Asked Questions

How do I size a transformer?

Add up the load in kVA (kW ÷ power factor, or √3 × V × I for three-phase), add a margin for growth, and pick the next standard size at or above it. A 40 kVA load with a 25% margin needs 50 kVA, so a 75 kVA three-phase unit is the next standard size. A licensed electrician or engineer confirms the demand load under the electrical code.

What are the standard transformer sizes?

Common single-phase sizes are 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 667, 833 kVA; common three-phase sizes are 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1,000, 1,500, 2,000, 2,500 kVA. Manufacturers make others, and not every size comes in every voltage combination.

How do I calculate full-load current?

Divide the rating in VA by the voltage, and by √3 as well for three-phase. A 75 kVA three-phase transformer, 600 V to 208 V, has full-load currents of 72.17 A on the primary and 208.2 A on the secondary.

What is the turns ratio?

The ratio of primary to secondary turns, which equals the voltage ratio in an ideal transformer: Vp ÷ Vs = Np ÷ Ns. A pole-top transformer from 7,200 V to 240 V has a ratio of 30 : 1, so a 1,500-turn primary needs 50 secondary turns. The currents go the other way: 150 A on the secondary is 5 A on the primary.

Why size by kVA and not kW?

A transformer heats up with current, which depends on the apparent power (kVA), not only the real power (kW). A 36 kW motor load at a power factor of 0.8 is 45 kVA, so it needs a bigger transformer than 36 kW of heaters.

Does the calculator size the breaker or fuses?

No. Overcurrent protection on the primary and secondary, conductor sizes and grounding depend on the transformer’s impedance, inrush, the conductors and local rules, and are set by the Canadian Electrical Code (Section 26) or the US National Electrical Code (Article 450.3). That is a licensed electrician’s or engineer’s job.

What does reflected impedance mean?

A load on the secondary looks larger from the primary by the square of the turns ratio: Z_primary = a² × Z_secondary. It is how transformers match impedances, for example in audio output transformers. In the default 600 V to 208 V example, the 1.082 Ω per-phase load looks like 9 Ω from the primary.

How efficient are transformers?

Large distribution transformers are among the most efficient machines made, typically 97 to 99% at full load. The losses split into core losses, which are there whenever the transformer is energised, and copper losses, which grow with the square of the load. Efficiency standards in Canada (NRCan) and the US (DOE) set minimum values by size.

Uses the ideal-transformer relations of OpenStax University Physics Vol. 2 §15.6 and the full-load current formulas I = kVA × 1,000 ÷ V (÷ √3 for three-phase). Standard sizes are the common ratings in manufacturer catalogues (not read from the IEEE C57.12 or CSA C2 tables themselves). The growth margin is design practice, not a code rule. It leaves out demand factors and the code load calculation, harmonic (K-factor) and motor-starting loads, ambient temperature and altitude derating, impedance and voltage regulation, and the sizing of overcurrent protection, conductors and grounding (CEC Section 26, NEC 450.3): a licensed electrician sizes the protection.

Transformer Sizing Calculator: kVA, Standard Sizes, Full-Load Current and Turns Ratio

By FindMySum · Last reviewed

A transformer has to carry its load without overheating, so choosing one starts with a simple question: how many kilovolt-amperes does the load draw? This transformer sizing calculator turns your load, given in kVA, in kW with a power factor, or in amps, into the next standard transformer size, adds a growth margin, and shows the full-load current on both sides, the turns ratio and how heavily the chosen size is loaded. It works for single-phase and three-phase transformers at any voltages.

Step 1: the load in kVA

Transformers are rated in apparent power, kVA, because their heating depends on the current, whatever the power factor. Convert your load:

  • from real power: kVA = kW ÷ power factor
  • from current, single-phase: kVA = V × I ÷ 1,000
  • from current, three-phase: kVA = √3 × V × I ÷ 1,000, with V the line-to-line voltage

A 36 kW load of heaters (power factor 1) is 36 kVA. The same 36 kW of motors at a power factor of 0.8 is 45 kVA, which needs a noticeably bigger transformer.

Step 2: margin and the next standard size

Designers rarely size a transformer exactly to today's load. The calculator adds a growth margin, 25% by default, which is common practice rather than a code requirement. It then picks the smallest standard rating at or above the result. Common sizes are:

  • single-phase: 3, 5, 7.5, 10, 15, 25, 37.5, 50, 75, 100, 167, 250, 333, 500, 667 and 833 kVA
  • three-phase: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1,000, 1,500, 2,000 and 2,500 kVA

The odd-looking values follow a preferred-number series, which is why 37.5 and 112.5 kVA exist.

Step 3: full-load current

Each size has a full-load current (FLA) on each winding:

  • single-phase: I = kVA × 1,000 ÷ V
  • three-phase: I = kVA × 1,000 ÷ (√3 × V)

These currents are the starting point for the electrician's protection and conductor design.

Worked example: a 600 V to 120/208 V transformer

Canadian commercial buildings are usually supplied at 600 V three-phase, and a dry-type transformer steps it down to 120/208 V for receptacles and lighting. Suppose the panel's load is 40 kVA:

  • required size = 40 × 1.25 = 50 kVA, so the next standard size is 75 kVA
  • primary FLA = 75,000 ÷ (√3 × 600) = 72.2 A
  • secondary FLA = 75,000 ÷ (√3 × 208) = 208.2 A
  • today's load uses 40 ÷ 75 = 53% of the rating
  • turns ratio = 600 ÷ 208 = 2.88 : 1

In the United States the same panel would usually be fed from 480 V, with a primary FLA of 90.2 A for the same 75 kVA unit.

Turns ratio and the ideal transformer

In an ideal transformer, the voltage per turn is the same on both windings, so

  • Vp ÷ Vs = Np ÷ Ns = Is ÷ Ip

Voltage steps down by the turns ratio and current steps up by the same factor, keeping the power the same. A utility pole-top transformer from 7,200 V to 240 V has a ratio of 30 : 1; a house drawing 150 A takes only 5 A from the primary line. Enter a number of primary turns and the calculator gives the secondary turns you need.

A load impedance on the secondary also appears larger from the primary, by the square of the turns ratio. This is how audio and radio transformers match a low-impedance speaker or antenna to a high-impedance amplifier.

Efficiency and losses

Real transformers lose a little energy as heat in the core and the windings. Distribution transformers typically run at 97 to 99% efficiency. Enter an efficiency and the calculator shows the power drawn from the supply and the losses at your load. Core losses are present whenever the transformer is energised, even with no load, so an oversized transformer that runs lightly loaded all year wastes energy too.

What this calculator does not do

Sizing the transformer is only part of the installation. The overcurrent protection on the primary and secondary, the conductor sizes, grounding and bonding, the vault or enclosure and the clearances are set by the electrical code: Section 26 of the Canadian Electrical Code (CSA C22.1) and Article 450 of the US National Electrical Code (NFPA 70), as adopted by your province, state or city. Those depend on details such as the transformer's impedance and inrush current, and they are work for a licensed electrician or engineer. The calculator also leaves out code demand factors, harmonic loads that call for K-rated transformers, motor starting, and derating for heat and altitude.

More questions

Can I run a transformer at 100% of its rating?

Transformers are designed to carry their nameplate kVA continuously at rated ambient temperature, so yes. Designers usually leave headroom anyway, for future load, for hot rooms and for harmonic currents from electronics, which heat a transformer more than their kVA suggests. Many keep normal loading around 60 to 80% of the rating.

What is a 120/208 V system?

A three-phase, four-wire wye secondary: 208 V between any two phase conductors and 120 V from each phase to neutral, because 208 ÷ √3 = 120. It is the standard supply for receptacles and lighting in Canadian and US commercial buildings, often fed by a dry-type transformer from 600 V (Canada) or 480 V (US).

Can a transformer be used backwards to step voltage up?

Many dry-type transformers can be back-fed, but not all, and the manufacturer has to approve it: inrush current is higher, taps work in reverse and the neutral connection may not be available. Use a transformer designed for step-up when you can.

Why does a transformer hum?

Magnetostriction: the steel core changes length very slightly as it is magnetised, twice per cycle. On a 60 Hz supply the fundamental hum is 120 Hz, with harmonics. Loose laminations or mounting make it louder; that is why transformer rooms often have vibration isolators.

What is transformer impedance on the nameplate?

The percent impedance (%Z) is the share of rated voltage needed on the primary to drive full-load current through a shorted secondary. It sets the available fault current, roughly full-load current × 100 ÷ %Z, and the voltage drop under load. It matters for breaker interrupting ratings, which is part of the electrician's protection design.

Does a transformer change the frequency?

No. A transformer changes voltage and current but passes the frequency through unchanged. A 60 Hz appliance used on a 50 Hz supply through a transformer still runs at 50 Hz, which can matter for motors and clocks.