Snow Load Calculator: How Much Snow Your Roof Is Carrying
By FindMySum · Last reviewed
After a big storm, or a week of snow followed by rain, many homeowners look up at the roof and wonder how much it is carrying. This calculator answers two questions: how much the snow there now weighs, and how that compares with the snow load the building code expects a roof like yours to carry. It is a planning and safety tool, not a structural design.
Step 1: the weight of the snow there now
Snow weight depends far more on the type of snow than on its depth. The density of snow ranges widely:
| Snow | Typical density |
|---|---|
| Fresh, dry powder (fallen in calm, cold air) | 50–70 kg/m³ |
| Damp new snow | 100–200 kg/m³ |
| Settled snow | 200–300 kg/m³ |
| Wind-packed snow | 350–400 kg/m³ |
| Wet, heavy or old granular snow | 400–830 kg/m³ |
| Ice | up to 917 kg/m³ |
These ranges come from glaciology (Paterson, The Physics of Glaciers). The load on each square metre is the density times the depth in metres:
load (kg/m²) = density × depth
To get kilopascals, multiply by the acceleration of gravity, 9.80665, and divide by 1,000. To get pounds per square foot, divide the kilopascals by 0.0479.
Worked example (the Canadian default). 30 cm of settled snow at 250 kg/m³ is 250 × 0.30 = 75 kg/m², which is 0.74 kPa or 15.4 psf. On a roof 12 m by 9 m in plan (108 m²), that is about 8,100 kg: the weight of five or six cars.
Measure the roof in plan, the way you would see it from above, not along the slope: snow loads are defined per square metre of horizontal area.
Step 2: the code roof snow load
Houses and small buildings: NBC Part 9
Most Canadian houses are designed under Part 9 of the National Building Code. Article 9.4.2.2 gives the specified snow load as:
S = Cb × Ss + Sr
- Ss is the 1-in-50-year ground snow load for your location, and Sr the associated rain load, both from Appendix C of the code or your province's table.
- Cb is the basic roof snow load factor: 0.45 where the entire width of the roof is 4.3 m or less, and 0.55 for all other roofs.
- The result is never less than 1 kPa.
For Toronto (City Hall), Ss is 0.9 kPa and Sr 0.4 kPa, so S = 0.55 × 0.9 + 0.4 = 0.895 kPa, which rises to the 1 kPa minimum. The example's 0.74 kPa of settled snow is about 74% of that. It would take about 41 cm of settled snow, or about 20 cm of wet snow, to reach it.
Engineered buildings: NBC Part 4
Larger buildings, and anything Part 9 does not cover, use Sentence 4.1.6.2.(1):
S = Is × [Ss × (Cb × Cw × Cs × Ca) + Sr]
- Cb is 0.8 for most roofs. For large roofs it grows, because snow does not blow off the middle of a big roof: with the characteristic length lc = 2w − w²/l (w and l the smaller and larger plan dimensions), Cb = (1/Cw)·[1 − (1 − 0.8·Cw)·e^(−(lc·Cw² − 70)/100)] when lc is over 70/Cw².
- Cw, the wind exposure factor, is 1.0, or 0.75 for fully exposed rural roofs and 0.5 north of the treeline, but only for low- and normal-importance buildings with no parapets or drifting.
- Cs, the slope factor, is 1 up to 30°, then (70° − slope)/40°, reaching zero at 70°. For unobstructed slippery roofs it is 1 up to 15°, then (60° − slope)/45°.
- Ca is 1 for the uniform load; drifts and valleys use higher values that this calculator does not model.
- Is, the importance factor, is 0.8, 1.0, 1.15 or 1.25 for the strength check (low, normal, high, post-disaster) and 0.9 for serviceability.
- Sr is never more than Ss × Cb × Cw × Cs × Ca.
United States: ASCE 7-22
In the US the flat-roof snow load is pf = 0.7 × Ce × Ct × pg, where pg is the ground snow load from the ASCE Hazard Tool for your risk category, Ce the exposure factor and Ct the thermal factor. The 2022 edition removed the separate importance factor; risk is now built into the ground snow maps. A sloped roof carries ps = Cs × pf. Enter pg for your site; the page does not include US maps.
NBC 2020 or NBC 2025
The calculator uses NBC 2020 by default because it is the edition in force in most provinces and territories in 2026; Newfoundland and Labrador enforces NBC 2025, and other provinces will adopt it on their own schedules. Choose the edition next to the design rule.
NBC 2025 changes how the snow load is set. Instead of a 1-in-50-year ground snow load multiplied by a load factor of 1.5, Appendix C now lists 1-in-1,000-year values that are used with a load factor of 1.0, which evens out the risk between regions. For a house under Part 9 the formula becomes S = (Cb × Ss + Sr) ÷ 1.5, still at least 1 kPa, and that load is multiplied by 1.5 again if a member is designed to Part 4. In Ottawa the 1-in-1,000-year Ss is 3.4 kPa and Sr 0.6 kPa, so a wide roof gets (0.55 × 3.4 + 0.6) ÷ 1.5 = 1.65 kPa, close to the 1.72 kPa of NBC 2020.
For engineered buildings, Part 4 adds two factors. The wind exposure factor Cw now comes from the winter average temperature and wind speed in Table C-2, so cold, windy prairie sites get less snow on the roof (Regina about 0.61) while sheltered roofs and High or Post-disaster buildings keep at least 1.0. The thermal factor CT reduces the load on a warm roof that loses heat to the snow, between 0.7 and 1.0, and is 1.0 when the indoor temperature or the roof U-value is not known. The importance factor at the serviceability limit state is 0.6 for every category.
Reading the result
- Well below the code load: a roof in good condition is carrying a normal winter load.
- Approaching or above it: do not wait for more snow, and especially not for rain. Clear snow from the ground with a roof rake, or hire someone insured to do it.
- Signs of trouble at any load: sagging ridges or ceilings, new cracks in drywall, doors that stick, popping or creaking sounds. Leave the building and call a professional.
Code loads already include safety margins, so reaching 100% does not mean collapse; but a 1-in-50-year design value is the load the roof was meant to carry, and old, damaged or altered roofs may carry less.
What the calculator leaves out
Real roofs get uneven loads that the uniform formula does not show: drifts beside higher walls and roofs, extra snow in valleys and behind parapets, sliding snow from a roof above, and unbalanced loads on gable roofs when wind strips one side. Provinces and municipalities amend the national code, and the 2025 edition changes the snow-load basis. Your building official and a structural engineer decide the load for a real design.
More questions
Is the ground snow load the same as the roof snow load?
No. The ground snow load (Ss in Canada, pg in the US) is measured on open ground. Roofs usually carry less because wind blows snow off and heat from the building melts some of it, so the codes multiply the ground load by factors such as Cb (0.55 for most Part 9 roofs) or 0.7·Ce·Ct in ASCE 7. Drifts can make parts of a roof carry far more than the ground.
How do I find Ss and Sr for my town?
Appendix C of the National Building Code of Canada lists Ss and Sr for about 680 locations, and provinces publish their own tables (Ontario's Supplementary Standard SB-1, the BC Building Code's Appendix C). Many municipalities post their design values on their building permit pages. Use the value for the closest listed location at a similar elevation, or ask your building department.
Can a roof collapse under snow?
It is rare for a roof built to code and in good repair, because design loads include safety factors and are based on a 1-in-50-year snowfall. Collapses usually happen with drifts against higher walls, rain soaking a deep snow pack, poor construction, rot or damage, or flat roofs on older and agricultural buildings. Watch for sagging, cracks and sticking doors.
How deep can snow get before it reaches the design load?
The calculator answers this for each type of snow. For a Toronto house with a 1 kPa Part 9 load, about 41 cm of settled snow or 20 cm of wet, heavy snow reaches it. Light fresh powder would need well over a metre, which is why the type of snow matters more than the depth.
Does the NBC 2025 change these numbers?
Yes, and the page lets you choose. NBC 2025 lists 1-in-1,000-year ground snow and rain loads (Ottawa's Ss goes from 2.4 to 3.4 kPa) and applies them with a load factor of 1.0 instead of multiplying 1-in-50-year values by 1.5. For houses, Part 9 divides the result by 1.5, so a typical Ottawa roof moves from 1.72 to 1.65 kPa. Part 4 adds a wind exposure factor from the winter temperature and wind speed and a thermal factor for heat lost through the roof. NBC 2020 stays the default because it is the edition in force in most provinces; Newfoundland and Labrador has enforced NBC 2025 since July 12, 2026. Check the edition your building department uses.
Sources
- National Research Council Canada: National Building Code of Canada 2020
- British Columbia Building Code 2018, Division B, Part 4 (Article 4.1.6.2) and Appendix C
- Science Learning Hub: Snow and ice density (after Paterson, The Physics of Glaciers)
- American Society of Civil Engineers: ASCE/SEI 7-22 Minimum Design Loads