Skip to content

CFM Calculator

Airflow in CFM, L/s and m³/h from room size and air changes per hour, plus bathroom fan, range hood and whole-house ventilation sizing (HVI, ASHRAE 62.2, NBC 2020 or 2025 Subsection 9.32.3).

Calculator Details

Airflow:118.7 CFMSee results ↓

Airflow for a room, air changes from a fan, a bathroom fan, a range hood, or whole-house ventilation

Metres or feet

Inside length of the room

Inside width of the room

Floor to ceiling

How many times an hour the room’s air is replaced (e.g. 8 for a bathroom, 6–8 for a workshop)

Your Results

Airflow: 118.7 CFM

Airflow

118.7 CFM

56 L/s · 202 m³/h

Litres per second

56 L/s

Air changes per hour

6.00

Room volume

33.6 m³

1186.6 ft³

Rated CFM is at a set static pressure; long or narrow ducts and elbows lower real airflow, so pick a fan with some margin and short, smooth ducting.

To change the air 6 times an hour in a 1186.6 ft³ (33.6 m³) room you need 118.7 CFM (56 L/s, 202 m³/h).

Compare scenarios

Save these inputs as a scenario, change them, and compare the results side by side.

Loading, available in a moment

Detailed Breakdown

Your result and NBC 2020 exhaust requirements
RequirementCFML/sSource
Your result (you)118.756.0Volume × ACH ÷ 60
Bathroom exhaust fan (NBC 9.32.3.7)53.025.0NBC 2020
Kitchen exhaust (NBC 9.32.3.7)105.950.0NBC 2020
Principal exhaust, 1 bedroom (minimum; maximum 24 L/s)33.916.0NBC 2020 Table 9.32.3.3
Principal exhaust, 2 bedrooms (minimum; maximum 28 L/s)38.118.0NBC 2020 Table 9.32.3.3
Principal exhaust, 3 bedrooms (minimum; maximum 32 L/s)46.622.0NBC 2020 Table 9.32.3.3
Principal exhaust, 4 bedrooms (minimum; maximum 38 L/s)55.126.0NBC 2020 Table 9.32.3.3
Principal exhaust, 5 bedrooms (minimum; maximum 45 L/s)63.630.0NBC 2020 Table 9.32.3.3

Check your provincial or local code: some provinces (e.g. Ontario, Quebec) have their own ventilation rules.

How This Calculator Works

How the airflow is calculated

CFM = room volume (ft³) × air changes per hour ÷ 60

1 CFM = 0.4719 L/s = 1.699 m³/h

Your numbers: 1186.6 ft³ × 6 ÷ 60 = 118.7 CFM.

Frequently Asked Questions

How do I calculate CFM for a room?

Multiply the room’s volume in cubic feet (length × width × height) by the number of air changes you want per hour, then divide by 60 minutes. A 12 × 12 × 8 ft room is 1,152 ft³; at 6 air changes per hour it needs 1,152 × 6 ÷ 60 = 115 CFM.

How many CFM do I need for a bathroom fan?

The Home Ventilating Institute recommends 1 CFM per square foot of floor for bathrooms up to 100 ft², and at least 50 CFM. For larger bathrooms, add 50 CFM for each toilet, shower and tub and 100 CFM for a jetted tub.

What does the building code require for bathroom and kitchen fans in Canada?

Under the National Building Code of Canada (2020 and 2025 editions, Article 9.32.3.7), a bathroom exhaust fan needs 25 L/s (about 50 CFM) and a kitchen exhaust 50 L/s (about 100 CFM). The principal exhaust fan of the whole-house system is sized by bedrooms: 22–32 L/s for three bedrooms. Provinces that write their own code may differ.

Should I use NBC 2020 or NBC 2025?

Use the edition your province or territory has adopted. As of November 10, 2026, Newfoundland and Labrador (since July 12, 2026) is on NBC 2025; Nunavut (since September 8, 2018) still uses an older edition; every other province and territory is on NBC 2020 or a provincial code based on it (Ontario, Quebec, Alberta and British Columbia publish their own). The ventilation figures in Subsection 9.32.3 are the same in both editions, so the result doesn’t change.

What does ASHRAE 62.2 require?

ASHRAE 62.2-2022, the basis of most US residential ventilation codes, asks for continuous whole-house ventilation of 0.03 CFM per ft² of floor plus 7.5 CFM per occupant (bedrooms + 1). Bathrooms need 50 CFM on demand or 20 CFM continuous; a vented kitchen range hood 100 CFM.

How do I convert CFM to L/s or m³/h?

One cubic foot per minute is 0.4719 litres per second and 1.699 cubic metres per hour. Multiply CFM by 0.4719 for L/s, or divide L/s by 0.4719 (multiply by 2.119) for CFM. Canadian codes and many fan labels use L/s; US labels use CFM.

How big should my range hood be?

HVI suggests 100 CFM per foot of cooktop width for a hood against a wall and 150 CFM per foot over an island, because air is drawn from all sides. A 30 in (76 cm) range works out to 250 CFM. Powerful hoods may need make-up air in tight homes: check your local code.

How many air changes per hour should a room have?

It depends on the use. Bathroom fans sized at 1 CFM per square foot give about 8 air changes per hour with an 8 ft ceiling. Workshops and garages are often ventilated at 6–10, and whole-house ventilation provides well under 1 air change per hour on average. Follow the code or the equipment maker for specific uses.

Bathroom and range hood sizing from the Home Ventilating Institute; whole-house rates from ASHRAE 62.2-2022 (US) and the National Building Code of Canada 2020 or 2025, Subsection 9.32.3 (Canada; both editions read in NRC’s published text, and their ventilation figures are the same). It leaves out the ASHRAE infiltration credit, provincial codes that differ from the NBC (e.g. Ontario, Quebec, BC Step Code), CSA F326 design for six or more bedrooms, duct pressure losses, make-up air, heat recovery ventilator sizing and commercial ventilation. Your local building official has the final say.

CFM Calculator: Airflow, Air Changes and Fan Sizing

By FindMySum · Last reviewed

CFM, cubic feet per minute, is how fans, range hoods and ventilation systems are rated in North America. Canadian building codes use litres per second (L/s) and much of the world uses cubic metres per hour (m³/h), so this calculator shows all three. It works in five modes: the airflow needed for a room from air changes per hour, the air changes a fan gives you, bathroom fan sizing, range hood sizing and whole-house ventilation under the US (ASHRAE 62.2) or Canadian (NBC 2020 or NBC 2025) rules.

Airflow from air changes per hour

An air change per hour (ACH) means a volume of air equal to the room is exhausted or supplied once an hour. Since CFM is per minute:

CFM = room volume (ft³) × ACH ÷ 60

Worked example (the Canadian default). A room 4 m × 3.5 m with a 2.4 m ceiling is 33.6 m³, or 1,186.6 ft³. At 6 air changes per hour: 1,186.6 × 6 ÷ 60 = 118.7 CFM, which is 56.0 L/s or 202 m³/h. The US default, a 12 × 12 ft room with an 8 ft ceiling, needs 115 CFM at the same rate.

Turned around, ACH = CFM × 60 ÷ volume: an 80 CFM fan in a 10 × 8 × 8 ft room gives 7.5 air changes an hour.

Units

One cubic foot is 0.0283168 m³ (exactly 0.3048³), so:

  • 1 CFM = 0.4719 L/s; 1 L/s = 2.119 CFM
  • 1 CFM = 1.699 m³/h; 1 m³/h = 0.5886 CFM

Bathroom fans

The Home Ventilating Institute (HVI) recommends 1 CFM per square foot of floor for bathrooms up to 100 ft², with at least 50 CFM. With an 8 ft ceiling that is about 8 air changes an hour. A 3 × 2.5 m Canadian bathroom (80.7 ft²) needs about 81 CFM; a small 5 × 8 ft powder room gets the 50 CFM minimum.

Above 100 ft², HVI sizes by fixture: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. A large bathroom with a toilet, shower and tub needs 150 CFM, which can be one fan or separate fans over the shower and toilet.

Codes set a floor too. The National Building Code of Canada 2020 requires 25 L/s (about 50 CFM) of exhaust in a bathroom, and ASHRAE 62.2 asks for 50 CFM on demand or 20 CFM running continuously.

Range hoods

HVI's rule of thumb is 100 CFM per foot of cooktop width for a hood against a wall and 150 CFM per foot over an island, where cross-drafts carry smoke away from the hood. A standard 30 in (76 cm) range needs about 250 CFM against a wall; a 36 in island cooktop about 450 CFM. Codes set minimums: 50 L/s (about 100 CFM) of kitchen exhaust under the NBC, and 100 CFM for a vented range hood under ASHRAE 62.2. Very powerful hoods can require make-up air.

Whole-house ventilation

Modern, airtight homes need mechanical ventilation to remove moisture and pollutants.

United States: ASHRAE 62.2. The total continuous ventilation rate is 0.03 CFM per square foot of floor plus 7.5 CFM per occupant, counting bedrooms plus one. A 2,000 ft² home with three bedrooms needs 0.03 × 2,000 + 7.5 × 4 = 90 CFM. The full standard lets you subtract a credit for measured air leakage, which this calculator leaves out.

Canada: National Building Code, Subsection 9.32.3. The principal exhaust fan must be able to run within a range set by the number of bedrooms: 16–24 L/s for one bedroom, 18–28 for two, 22–32 for three, 26–38 for four and 30–45 for five. Homes with six or more bedrooms are designed to CSA F326. A three-bedroom home therefore needs a principal fan of at least 22 L/s (47 CFM). Some provinces publish their own codes with different requirements, so check with your municipality.

NBC 2020 or NBC 2025? The calculator lets you pick the edition. NBC 2020 is the default because most provinces and territories still enforce it, or a provincial code built on it. The 2025 edition, published by the National Research Council in December 2025, is being adopted province by province over the following years; Newfoundland and Labrador was the first. We compared the two texts of Subsection 9.32.3 line by line: the principal fan table, the 50 L/s kitchen and 25 L/s bathroom exhaust rates and the six-bedroom limit are unchanged, so both editions give the same answer. Other parts of the 2025 code did change, notably snow loads, which now use 1-in-1,000-year values.

Getting the real airflow

A fan's rated CFM is measured at a set static pressure, often 0.1 in of water for bath fans. Every metre of duct, elbow and cap adds resistance and reduces the real airflow, sometimes by half. Choose a fan rated at the pressure your duct run creates, keep ducts short, smooth and insulated in cold spaces, and make sure there's a path for replacement air, such as a gap under the bathroom door.

What the calculator leaves out

It doesn't model duct pressure losses, make-up air, heat recovery ventilator sizing, the ASHRAE infiltration credit, commercial ventilation, or provincial codes that differ from the NBC. Treat the result as a starting point and confirm with the fan's specifications and your local building official.

More questions

Why does my bathroom mirror still fog with the fan on?

The fan may be undersized, the duct may be long, crushed or full of elbows, or there may be no gap under the door for replacement air. A fan's rated airflow is measured at a low static pressure; real installations often deliver much less. Run the fan during the shower and for 20 minutes after, and check that the duct ends outside, not in the attic.

Is a bigger bathroom fan always better?

Not necessarily. A fan far larger than needed can be noisy and, in a tight house, can depressurize the home and pull combustion gases from fuel-burning appliances. Size to the rule, pick a quiet fan (look at the sone rating) and duct it well.

What is a sone?

A sone is a measure of perceived loudness. Bath fans rated at 1 sone or less are quiet enough that people are more likely to run them. HVI-certified fans list both airflow and sones on the box.

Do I need make-up air for a big range hood?

Many codes require make-up air when a kitchen exhaust exceeds a set flow, because a powerful hood in a tight house can backdraft a furnace, water heater or fireplace. The threshold varies; in the US it is often 400 CFM. Ask your building department before installing a large hood.

What is the difference between an HRV and an exhaust fan?

An exhaust fan only removes air; replacement air leaks in wherever it can. A heat recovery ventilator (HRV) or energy recovery ventilator (ERV) exhausts stale air and supplies fresh air through a heat exchanger, recovering most of the heat. Many new Canadian homes use an HRV as the principal ventilation system.

Sources

This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.

Spotted a wrong result or a bug? Report a problem

May we count your visits with Invoker Analytics? It keeps a random visitor number in your browser. Your calculator inputs are never sent. Privacy policy