CFM Calculator: Airflow, Air Changes and Fan Sizing
By FindMySum · Last reviewed
CFM, cubic feet per minute, is how fans, range hoods and ventilation systems are rated in North America. Canadian building codes use litres per second (L/s) and much of the world uses cubic metres per hour (m³/h), so this calculator shows all three. It works in five modes: the airflow needed for a room from air changes per hour, the air changes a fan gives you, bathroom fan sizing, range hood sizing and whole-house ventilation under the US (ASHRAE 62.2) or Canadian (NBC 2020 or NBC 2025) rules.
Airflow from air changes per hour
An air change per hour (ACH) means a volume of air equal to the room is exhausted or supplied once an hour. Since CFM is per minute:
CFM = room volume (ft³) × ACH ÷ 60
Worked example (the Canadian default). A room 4 m × 3.5 m with a 2.4 m ceiling is 33.6 m³, or 1,186.6 ft³. At 6 air changes per hour: 1,186.6 × 6 ÷ 60 = 118.7 CFM, which is 56.0 L/s or 202 m³/h. The US default, a 12 × 12 ft room with an 8 ft ceiling, needs 115 CFM at the same rate.
Turned around, ACH = CFM × 60 ÷ volume: an 80 CFM fan in a 10 × 8 × 8 ft room gives 7.5 air changes an hour.
Units
One cubic foot is 0.0283168 m³ (exactly 0.3048³), so:
- 1 CFM = 0.4719 L/s; 1 L/s = 2.119 CFM
- 1 CFM = 1.699 m³/h; 1 m³/h = 0.5886 CFM
Bathroom fans
The Home Ventilating Institute (HVI) recommends 1 CFM per square foot of floor for bathrooms up to 100 ft², with at least 50 CFM. With an 8 ft ceiling that is about 8 air changes an hour. A 3 × 2.5 m Canadian bathroom (80.7 ft²) needs about 81 CFM; a small 5 × 8 ft powder room gets the 50 CFM minimum.
Above 100 ft², HVI sizes by fixture: 50 CFM for each toilet, shower and bathtub and 100 CFM for a jetted tub. A large bathroom with a toilet, shower and tub needs 150 CFM, which can be one fan or separate fans over the shower and toilet.
Codes set a floor too. The National Building Code of Canada 2020 requires 25 L/s (about 50 CFM) of exhaust in a bathroom, and ASHRAE 62.2 asks for 50 CFM on demand or 20 CFM running continuously.
Range hoods
HVI's rule of thumb is 100 CFM per foot of cooktop width for a hood against a wall and 150 CFM per foot over an island, where cross-drafts carry smoke away from the hood. A standard 30 in (76 cm) range needs about 250 CFM against a wall; a 36 in island cooktop about 450 CFM. Codes set minimums: 50 L/s (about 100 CFM) of kitchen exhaust under the NBC, and 100 CFM for a vented range hood under ASHRAE 62.2. Very powerful hoods can require make-up air.
Whole-house ventilation
Modern, airtight homes need mechanical ventilation to remove moisture and pollutants.
United States: ASHRAE 62.2. The total continuous ventilation rate is 0.03 CFM per square foot of floor plus 7.5 CFM per occupant, counting bedrooms plus one. A 2,000 ft² home with three bedrooms needs 0.03 × 2,000 + 7.5 × 4 = 90 CFM. The full standard lets you subtract a credit for measured air leakage, which this calculator leaves out.
Canada: National Building Code, Subsection 9.32.3. The principal exhaust fan must be able to run within a range set by the number of bedrooms: 16–24 L/s for one bedroom, 18–28 for two, 22–32 for three, 26–38 for four and 30–45 for five. Homes with six or more bedrooms are designed to CSA F326. A three-bedroom home therefore needs a principal fan of at least 22 L/s (47 CFM). Some provinces publish their own codes with different requirements, so check with your municipality.
NBC 2020 or NBC 2025? The calculator lets you pick the edition. NBC 2020 is the default because most provinces and territories still enforce it, or a provincial code built on it. The 2025 edition, published by the National Research Council in December 2025, is being adopted province by province over the following years; Newfoundland and Labrador was the first. We compared the two texts of Subsection 9.32.3 line by line: the principal fan table, the 50 L/s kitchen and 25 L/s bathroom exhaust rates and the six-bedroom limit are unchanged, so both editions give the same answer. Other parts of the 2025 code did change, notably snow loads, which now use 1-in-1,000-year values.
Getting the real airflow
A fan's rated CFM is measured at a set static pressure, often 0.1 in of water for bath fans. Every metre of duct, elbow and cap adds resistance and reduces the real airflow, sometimes by half. Choose a fan rated at the pressure your duct run creates, keep ducts short, smooth and insulated in cold spaces, and make sure there's a path for replacement air, such as a gap under the bathroom door.
What the calculator leaves out
It doesn't model duct pressure losses, make-up air, heat recovery ventilator sizing, the ASHRAE infiltration credit, commercial ventilation, or provincial codes that differ from the NBC. Treat the result as a starting point and confirm with the fan's specifications and your local building official.
More questions
Why does my bathroom mirror still fog with the fan on?
The fan may be undersized, the duct may be long, crushed or full of elbows, or there may be no gap under the door for replacement air. A fan's rated airflow is measured at a low static pressure; real installations often deliver much less. Run the fan during the shower and for 20 minutes after, and check that the duct ends outside, not in the attic.
Is a bigger bathroom fan always better?
Not necessarily. A fan far larger than needed can be noisy and, in a tight house, can depressurize the home and pull combustion gases from fuel-burning appliances. Size to the rule, pick a quiet fan (look at the sone rating) and duct it well.
What is a sone?
A sone is a measure of perceived loudness. Bath fans rated at 1 sone or less are quiet enough that people are more likely to run them. HVI-certified fans list both airflow and sones on the box.
Do I need make-up air for a big range hood?
Many codes require make-up air when a kitchen exhaust exceeds a set flow, because a powerful hood in a tight house can backdraft a furnace, water heater or fireplace. The threshold varies; in the US it is often 400 CFM. Ask your building department before installing a large hood.
What is the difference between an HRV and an exhaust fan?
An exhaust fan only removes air; replacement air leaks in wherever it can. A heat recovery ventilator (HRV) or energy recovery ventilator (ERV) exhausts stale air and supplies fresh air through a heat exchanger, recovering most of the heat. Many new Canadian homes use an HRV as the principal ventilation system.
Sources
- Home Ventilating Institute: How much ventilation do I need?
- ASHRAE: Addendum e to ANSI/ASHRAE Standard 62.2-2022 (local exhaust Tables 5-1 and 5-2)
- National Research Council Canada: National Building Code of Canada 2020
- National Research Council Canada: National Building Code of Canada 2025 (Government of Canada Publications)
- Canadian Board for Harmonized Construction Codes: provincial and territorial adoption
This article explains how the calculator works and is general information, not financial, tax, legal or medical advice. Rules change; check the sources above or a qualified professional before you act.